Instruction Manual

Troubleshooting 4-5
PowerFlex 400 Adjustable Frequency AC Drive FRN 1.xx - 7.xx User Manual
Publication 22C-UM001I-EN-P
Motor does not Start.
No. Fault
Type
(1)
Description Action
F81 Comm Loss
RS485 (DSI) port stopped
communicating.
1. Check RS485 wiring connection.
2. Check if a communications adapter
or HIM was disconnected.
3. Increase C106
[Comm Loss Time]
to an appropriate time for
application.
4. Change C105
[Comm Loss Action]
to a value other than “0” (fault), if
appropriate for the application.
F94 Function Loss
P036 [Start Source] is set to
setting 6. The input to terminal
01 has been opened.
Close input to terminal 01 and re-start
the drive.
F100 Parameter
Checksum
The checksum read from the
board does not match the
checksum calculated.
Set P041 [Reset To Defalts] to option 1
“Reset Defaults”.
F122 I/O Board Fail
Failure has been detected in
the drive control and I/O
section.
1. Cycle power.
2. Replace drive if fault cannot be
cleared.
(1)
See page 4-1 for a description of fault types.
Common Symptoms and Corrective Actions
Cause(s) Indication Corrective Action
No output voltage to the motor. None Check the power circuit.
Check the supply voltage.
Check all fuses and disconnects.
Check the motor.
Verify that the motor is connected properly.
Check the control input signals.
Verify that a Start signal is present. If
2-Wire control is used, verify that either the
Run Forward or Run Reverse signal is
active, but not both.
Verify that I/O Terminal 01 is active.
Verify that P036
[Start Source] matches
your configuration.
Verify that A166
[Reverse Disable] is not
prohibiting movement.
Drive is Faulted Flashing red status
light
Clear fault.
Press Stop
Cycle power
Set A197
[Fault Clear] to option 1 “Clear
Faults”.
Cycle digital input if T051
- T054 [Digital
Inx Sel] is set to option 7 “Clear Fault”.