PowerFlex 400 Adjustable Frequency AC Drive FRN 1.xx - 7.xx User Manual
Publication 22C-UM001I-EN-P
Advanced Display Group
d301 [Control Source] Related Parameter(s): P036, P038, T051-T054
Displays the active source of the Start Command and Speed Command which are normally defined
by the settings of P036
[Start Source] and P038 [Speed Reference] but may be overridden by digital
inputs. Refer to the flowcharts on pages 1-28
and 1-29 for details.
Values Default: Read Only
Min/Max: 0/99
Display: 1
Start Command Digit 0
0 = Keypad
1 = Terminal Block
2 = Communications
Speed Command Digit 1
0 = Local Keypad Potentiometer
1 = A142
[Internal Freq]
2 = Analog Input 1
3 = Analog Input 2
4 = A143
-A146 [Preset Freq x]
(T051
- T053 [Digital Inx Sel] must be set to 4)
5 = Communications
Reserved Digit 2
Reserved Digit 3
d302 [Contrl In Status] Related Parameter(s): b002, P036, T051-T054
Status of the control terminal block control inputs.
Important: Actual control commands may come from a source other than the control terminal block.
Values Default: Read Only
Min/Max: 0/1
Display: 1
1 = Condition True, 0 = Condition False
Start/FWD In I/O Terminal 02
Dir/REV In I/O Terminal 03
Stop Input I/O Terminal 01
Digital In 1 I/O Terminal 05
Digital In 2 I/O Terminal 06
Digital In 3 I/O Terminal 07
Digital In 4 I/O Terminal 08
Not Used