Instruction Manual

Programming and Parameters 3-53
PowerFlex 400 Adjustable Frequency AC Drive FRN 1.xx - 7.xx User Manual
Publication 22C-UM001I-EN-P
Advanced Program Group (continued)
A206 [ACT1 Minimum] Related Parameter(s): A204
(with FRN 7.xx and later.)
Sets the minimum value of the actual (ACT) 1 input. Used with the analog input min/max settings to
scale the analog input for use as the PID feedback. Can be used in a normal and inverted mode.
Values Default: 0.0%
Min/Max: 0.0/200.0%
Display: 0.1%
A207 [ACT1 Maximum]
ACT1 % Normal
A206 [ACT1 Minimum]
T070 [Analog In 1 Lo] T071 [Analog In 1 Hi]
A206 [ACT1 Minimum]
ACT1 % Inverted
A207 [ACT1 Maximum]
T070 [Analog In 1 Lo] T071 [Analog In 1 Hi]
A207 [ACT1 Maximum] Related Parameter(s): A204
(with FRN 7.xx and later.)
Sets the maximum value of the actual (ACT) 1 input.
Values Default: 100.0%
Min/Max: 0.0/200.0%
Display: 0.1%
A208 [ACT2 Minimum] Related Parameter(s): A205
(with FRN 7.xx and later.)
Sets the minimum value of the actual (ACT) 2 input. Used with the analog input min/max settings to
scale the analog input for use as the PID feedback. Can be used in a normal and inverted mode.
Values Default: 0.0%
Min/Max: 0.0/200.0%
Display: 0.1%
A209 [ACT2 Maximum]
ACT2 % Normal
A208 [ACT2 Minimum]
T074 [Analog In 2 Lo] T075 [Analog In 2 Hi]
A208 [ACT2 Minimum]
ACT2 % Inverted
A209 [ACT2 Maximum]
T074 [Analog In 2 Lo] T075 [Analog In 2 Hi]
A209 [ACT2 Maximum] Related Parameter(s): A205
(with FRN 7.xx and later.)
Sets the maximum value of the actual (ACT) 2 input.
Values Default: 100.0%
Min/Max: 0.0/200.0%
Display: 0.1%