Quick Start FRN 5.xx - 6.xx User Manual

Nederlands-19
A117 [Busreg.modus] 0/1 0 = “Uit” 1 = “Vrijgegeven” 1
A118 [Stroomgrens 2] 0,1/(A van drive × 1,8) 0,1 A A × 1,5
A119 [Skip Frequency] 0/400 Hz 1 Hz 0 Hz
A120 [Skip Freq Band] 0,0/30,0 Hz 0,1 Hz 0,0 Hz
A121 [Stall Fault Time] 0/5 0 = “60 sec”
1 = “120 sec”
2 = “240 sec”
3 = “360 sec”
4 = “480 sec”
5 = “Fout uit”
0
A122 [Verlies anal ing] 0/6 0 = “Uit”
1 = “Fout (F29)”
2 = “Stoppen”
3 = “Ref nul”
4 = “Ref min freq”
5 = “Ref max freq”
6 = “Ref int freq”
0
A123 [10 V bipol vrijg] 0/1 0 = “Unipolair in” 1 = “Bipolair in 0
A124 [Var PWM uit] 0/1 0 = “Vrijgegeven” 1 = “Uit” 0
A125 [Koppel prestatie mode] 0/1 0 = “V/Hz” 1 = “Sensrlz vect” 1
A126 [Motorstroom] 0,1/(A van drive × 2) 0,1 A Nominale A
A127 [Autotune] 0/2 0 = “Gereed/Idle”
1 = “Stat tunen”
2 = “Dynamisch tunen” 0
A128 [Spanningsval IR] 0,0/230,0 VAC 0,1 VAC Nominale V
A129 [Fluxstroomref] 0,00/[Motorstroom] 0,01 A Nominale A
A130 [PID trim hoog] 0.0/400.0 0.1 60.0
A131 [PID trim laag] 0.0/400.0 0.1 0.0
A132 [Sel PID ref] 0/8 0 = “PID uit”
1 = “PID setpunt”
2 = “0 – 10 V ing”
3 = “4 – 20 mA ing”
4 = “Comm.poort”
5 = “Setpnt, trim”
6 = “0 – 10 V, trim”
7 = “4 – 20 mA, trim”
8 = “Comm, trim”
0
A133 [Sel PID feedback] 0/2 0 = “0 – 10 V ing”
1 = “4 – 20 mA ing”
2 = “Comm.poort” 0
A134 [PID prop verst] 0.00/99.99 0.01 0.01
A135 [PID integ tijd] 0,0/999,9 Secs 0,1 sec 0,1 sec
A136 [PID diff snelh] 0,00/99,99 (1/sec) 0,01 (1/sec) 0,01 (1/sec)
A137 [PID setpunt] 0,0/100,0% 0,1% 0,0%
A138 [PID dode zone] 0,0/10,0% 0,1% 0,0%
A139 [PID voorbel] 0,0/400,0 Hz 0,1 Hz 0,0 Hz
A140-
A147
[Stp Logic 0 – 7] 0001/bAFF 4 cijfers
Raadpleeg de Gebruikershandleiding van de
PowerFlex 40 voor een lijst met cijferopties.
00F1
A150-
A157
[Stp Logic Time 0 – 7] 0,0/999,9 Secs 0,1 sec 30,0 sec
A160 [Vrtr EM rem uit] 0,01/10,00 Secs 0,01 sec 2,00 sec
A161 [Vrtr EM rem aan] 0,01/10,00 Secs 0,01 sec 2,00 sec
A162 [Sel MOP reset] 0/1 0 = “MOP ref nul” 1 = “Save MOP ref” 1
A163 [DB drempel] 0,0/110,0% 0,0% 100,0%
A164 [Comm.schrijfmodus] 0/1 0 = “Opslaan” 1 = “Alleen RAM” 0
A165 [Vrtrag anl verls] 0,0/20,0 Secs 0,1 sec 0,0 sec
A166 [Anal ing filter] 0/14 1 0
A167 [PID Invert Fout] 0/1 0 = “Niet inverted” 1 = “Inverted” 0
Nr. Parameter Min/Max Display/Opties Default
Zie de gebruikershandleiding van de PowerFlex 40 voor meer informatie over parameters.