Quick Start FRN 5.xx - 6.xx User Manual

Español-19
A111 [Anlg In 0–10 V Hi] 0.0/100.0 % 0.1 % 100.0 %
A112 [Anlg In 4–20 mA Lo] 0.0/100.0 % 0.1 % 0.0 %
A113 [Anlg In 4–20 mA Hi] 0.0/100.0 % 0.1 % 100.0 %
A114 [Slip Hertz @ FLA] 0.0/10.0 Hz 0.1 Hz 2.0 Hz
A115 [Process Time Lo] 0.00/99.99 0.01 0.00
A116 [Process Time Hi] 0.00/99.99 0.01 0.00
A117 [Bus Reg Mode] 0/1 0 = “Inhabilitado” 1 = “Habilitado” 1
A118 [Current Limit 2] 0.1/(Intens.Var × 1.8) 0.1 Amps Amps × 1.5
A119 [Skip Frequency] 0/400 Hz 1 Hz 0 Hz
A120 [Skip Freq Band] 0.0/30.0 Hz 0.1 Hz 0.0 Hz
A121 [Stall Fault Time] 0/5 0 = “60 Seconds
1 = “120 Seconds”
2 = “240 Seconds”
3 = “360 Seconds”
4 = “480 Seconds”
5 = “Flt Disabled”
0
A122 [Analog In Loss] 0/6 0 = “Disabled”
1 = “Fault (F29)”
2 = “Stop”
3 = “Zero Ref
4 = “Min Freq Ref”
5 = “Max Freq Ref
6 = “Int Freq Ref”
0
A123 [10 V Bipolar Enbl] 0/1 0 = “Uni-Polar In” 1 = “Bi-Polar In” 0
A124 [Var PWM Disable] 0/1 0 = “Enabled” 1 = “Disabled” 0
A125 [Torque Perf Mode] 0/1 0 = “V/Hz” 1 = “Sensrls Vect” 1
A126 [Motor NP FLA] 0.1/(Intens.Var × 2) 0.1 Amps Intens. Nominal
A127 [Autotune] 0/2 0 = “Ready/Idle”
1 = “Static Tune”
2 = “Rotate Tune” 0
A128 [IR Voltage Drop] 0.0/230.0 VCA 0.1 VCA Volts nomin var.
A129 [Flux Current Ref] 0.00/[Motor NP FLA] 0.01 Amps Intens. Nominal
A130 [PID Trim Hi] 0.0/400.0 0.1 60.0
A131 [PID Trim Lo] 0.0/400.0 0.1 0.0
A132 [PID Ref Sel] 0/8 0 = “PID Disabled”
1 = “PID Setpoint”
2 = “0–0 V Input”
3 = “4–20 mA Input”
4 = “Comm Port”
5 = “Setpnt, Trim”
6 = “0–10 V, Trim
7 = “4–20 mA, Trim”
8 = “Comm, Trim”
0
A133 [Sel realimnt PID] 0/2 0 = “0–10 V Input”
1 = “4–20 mA Input”
2 = “Comm Port” 0
A134 [PID Prop Gain] 0.00/99.99 0.01 0.01
A135 [PID Integ Time] 0.0/999.9 segundos 0.1 segundos 0.1 segundos
A136 [PID Diff Rate] 0.00/99.99 (1/seg) 0.01 (1/seg) 0.01 (1/seg)
A137 [PID Setpoint] 0.0/100.0 % 0.1 % 0.0 %
A138 [PID Deadband] 0.0/10.0 % 0.1 % 0.0 %
A139 [PID Preload] 0.0/400.0 Hz 0.1 Hz 0.0 Hz
A140-
A147
[Stp Logic 0–7] 0001/bAFF 4 Dígitos
Para obtener una lista de las opciones de dígitos,
consulte el documento PowerFlex 40 User Manual.
00F1
A150-
A157
[Stp Logic Time 0–7] 0.0/999.9 segundos 0.1 segundos 30.0 segundos
A160 [EM Brk Off Delay] 0.01/10.00 segundos 0.01 Seg 2.00 Seg
A161 [EM Brk On Delay] 0.01/10.00 segundos 0.01 Seg 2.00 Seg
A162 [MOP Reset Sel] 0/1 0 = “Zero MOP Ref 1 = “Save MOP Ref” 1
A163 [DB Threshold] 0.0/110.0 % 0.0 % 100.0 %
A164 [Comm Write Mode] 0/1 0 = “Save” 1 = “RAM Only” 0
A165 [Anlg Loss Delay] 0.0/20.0 segundos 0.1 segundos 0.0 segundos
A166 [Analog In Filter] 0/14 1 0
A167 [PID Invert Error] 0/1 0 = “Not Inverted” 1 = “Inverted” 0
No. Parámetro Mín./máx. Pantalla/opciones
Opción
predeterminada
en la fábrica
Consulte el documento PowerFlex 40 User Manual para más información sobre parámetros.