Owner's manual

Troubleshooting 4-5
PowerFlex 40 Adjustable Frequency AC Drive FRN 1.xx - 6.xx User Manual
Publication 22B-UM001H-EN-E
Motor does not Start.
F100 Parameter
Checksum
The checksum read from the
board does not match the
checksum calculated.
Set P041 [Reset To Defalts] to
option 1 “Reset Defaults”.
F122 I/O Board Fail
Failure has been detected in the
drive control and I/O section.
1. Cycle power.
2. Replace drive if fault cannot be
cleared.
(1)
See page 4-1 for a description of fault types.
No. Fault
Type
(1)
Description Action
Common Symptoms and Corrective Actions
Cause(s) Indication Corrective Action
No output voltage to the motor. None Check the power circuit.
Check the supply voltage.
Check all fuses and disconnects.
Check the motor.
Verify that the motor is
connected properly.
Check the control input signals.
Verify that a Start signal is
present. If 2-Wire control is used,
verify that either the Run
Forward or Run Reverse signal
is active, but not both.
Verify that I/O Terminal 01 is
active.
Verify that P036
[Start Source]
matches your configuration.
Verify that A095
[Reverse
Disable] is not prohibiting
movement.
Improper boost setting at initial
start-up.
None Set A084
[Boost Select] to option 2
“35.0, VT”.
Drive is Faulted Flashing red status light Clear fault.
Press Stop
Cycle power
Set A100
[Fault Clear] to option 1
“Clear Faults”.
Cycle digital input if A051
- A054
[Digital Inx Sel] is set to option 7
“Clear Fault”.
22B-UM001.book Page 5 Wednesday, January 22, 2014 11:04 AM