Specifications

PARAMETERS
No. Name Description
01 Reset Module Resets the adapter or sets the adapter parameters to factory default.
02 Comm Loss Action Sets the action that the adapter and drive will take if the adapter detects
a network failure.
03 Comm Loss Time Sets the communication loss timeout period (in seconds).
04 Flt Cfg Logic Sets the data that is sent to the drive if Parameter 02 - [Comm Loss Action]
05 Flt Cfg Ref is set to “Send Flt Cfg” and the adapter times out.
06 Baud Rate Cfg Sets the baud rate (kilobits per second) at which the adapter communicates.
07 Baud Rate Act Displays the baud rate (kilobits per second) actually used by the adapter.
08 MAC Address Displays the actual address selected by the MAC address switches
SW1 – SW7 on the adapter.
09 Max Master Sets the maximum MAC address for any device in the BACnet MS/TP token ring.
10 Max Info Frames Sets the maximum number of messages that the adapter can transmit while
it owns the token.
11 Device Inst Hi Sets the high-priority portion of the device instance number used by the adapter.
12 Device Inst Lo Sets the low-priority portion of the device instance number used by the adapter.
SPECIFICATIONS
Communications Network Protocol BACnet MS/TP
Data Rates 9600, 19200, 38400 or 76800 bps
Drive Protocol DSI
Data Rate 19.2 Kbps
Electrical Consumption Drive (DSI) 275 mA at 5 VDC
Network None
Regulatory BACnet BTL (BACnet Testing Laboratories)
approval pending
UL UL508C
cUL CAN/CSA C22.2 No. 14-M91
CE EN50178 and EN61800-3
CTick EN61800-3
UP = 1 = OPEN
MAC Address Switches
(SW1 - SW7)
Mode Switch (SW8)
Reserved for future use
1
5
6
7
8
4
3
2
SW1 Least Significant Bit (LSB) of MAC Address 0
Node 0
SW7 Most Significant Bit (MSB) of MAC Addres 0
SW8 Mode (reserved for future use)
SW2 Bit 1 of MAC Address 0
SW3 Bit 2 of MAC Address 0
SW4 Bit 3 of MAC Address 0
SW5 Bit 4 of MAC Address 0
SW6 Bit 4 of MAC Address 0
Switches Description Default
MAC ADDRESS SWITCHES
UP = OFF
TERM Switch (SW1)
-BIAS Switch (SW2) +BIAS Switch (SW3)
RSRV Switch (SW4)
Reserved for future use
1
4
3
2
SW1 Turns on/off the termination resistor Up (Off)
SW2 Turns on/off the -bias resistor Up (Off)
SW3 Turns on/off the +bias resistor Up (Off)
SW4 Reserved (not used)
Switches Description Default
TERMINATION/BIAS SWITCHES
Node 1 Node 2 Node "n"
SHLD
+B
-A
SHLD
+B
-A
SHLD
+B
-A
Terminal Signal Function
SHLD Termination Shield Termination
B Signal B TxRxD
A Signal A TxRxD
WIRING CONNECTIONS
Publication 22COMM-PP001D-EN-P – July 2006 Copyright ©2006 Rockwell Automation, Inc. All Rights Reserved. Printed in USA.
1203-USB or 22-SCM-232
Converter
PC Cable
Use DriveExplorer Lite or Full to configure a single
drive and its installed BACnet adapter.
Drive Cable
BACnet MS/TP Network
Use DriveExplorer Full to route through DSI and configure
drives connected directly on BACnet (Up to 127 drives!)
Laptop or Desktop PC
with DriveExplorer
PowerFlex 400 Drives with
22-COMM-B Adapters
NETWORK ROUTING EXAMPLE