PARAMETERS
No. Name Description
01 Send Service Pin Broadcasts a LON Service Pin message from the Neuron Chip to
provide the Neuron ID.
02 Neuron State Displays the state of the Neuron Chip
03 Reset Module Resets the adapter or sets the adapter parameters to factory default.
04 Neuron ID Displays the Neuron Chip ID.
05 Clear Counters Clears the network diagnostic counters.
06 Comm Flt Action Sets the action that the adapter will take if it detects that network
communications have been disrupted.
07 Flt Cfg Logic Sets the Logic Command data that is sent to the drive if Parameter 08
– [Comm Flt Action] is set to “Send Flt Cfg” and communications
are disrupted.
08 Flt Cfg Ref Sets the Speed Reference data that is sent to the drive if Parameter 08
– [Comm Flt Action] is set to “Send Flt Cfg” and communications
are disrupted.
09 Idle Flt Action Sets the action that the adapter and drive will take if the adapter detects
that the controller is in program mode. This setting is effective only if I/O
that controls the drive is transmitted through the adapter.
10 Idle Cfg Logic Sets the Logic Command data that is sent to the drive if Parameter 09
– [Idle Flt Action] is set to “Send Flt Cfg” and the controller is in
program mode.
11 Idle Cfg Ref Sets the Speed Reference data that is sent to the drive if Parameter 09
– [Idle Flt Action] is set to “Send Flt Cfg” and the controller is in
program mode.
12 RcvHrtBeat Time Sets the time used as a Receive Heartbeat timer and triggers the
fault action in Parameter 06 – [Comm Flt Action].
SPECIFICATIONS
Communications Drive Protocol LonWorks
Data Rate 78 Kbps
Drive Protocol DSI
Electrical Consumption Drive (DSI) 50 mA at 5 VDC
Network N/A
Regulatory UL UL508C
Compliance cUL CAN/CSA C22.2 No. 14-M91
CE EN61800-6-4: 2001, EN61000-6-2: 2001
VARIABLE SPEED MOTOR DRIVE PROFILES
nviObjRequest
SNVT_obj_request
Mandatory
Network
Variables
Node Object
nvoObjStatus
SNVT_obj_status
nv 1
nv 2
nc 50 - nciLocation
Optional
Configuration Properties
nviDrvSpeedStpt
SNVT_switch
Mandatory
Network
Variables
Optional
Network
Variables
Manufacturer-Defined
Network Variables
Variable Speed Motor
Drive: 6010
nvoDrvSpeed
SNVT_lev_percent
nviDrvSpeedScale
SNVT_lev_percent
nv 1
nv 3
nvoDrvCurnt
SNVT_amp
nv 4
nvoDrvVolt
SNVT_volt
nv 5
nvoDrvPwr
SNVT_power_kilo
nc 50 - nciMaxSpeed (mandatory)
nc 53 - nciMinSpeed (mandatory)
nc 48 - nciRcvHrtBt (optional)
nc 49 - nciSndHrtBt (mandatory)
nc 52 - nciMinOutTm (optional)
nc 158 - nciNmlSpeed (mandatory)
nc 159 - nciNmlFreq (mandatory)
nc 160 - nciRampUpTm (mandatory)
nc 161 - nciRampDownTM (mandatory)
nc 162 - nciDrvSpeedScale (optional)
Configuration Properties
nc 200 nciGenRdAdr
nc 200 nciGenWriAdr
nc 200 nciGenWriData
Manufacturer-Defined
Configuration Properties
nv 6
nvoDrvRunHours
SNVT_time_hour
nvoDrvStatus
SNVT_state
nv 7
nv 8
nvoDrvTemp
SNVT_temp_p
nv 9
nvoFreqAct
SNVT_freq_hz
nv 10
nvoDCBusVolt
SNVT_volt
nv 11
nvoDrvRunning
SNVT_switch
nvoAnalogInput1
SNVT_lev_percent
nvoAnalogInput2
SNVT_lev_percent
nvoDigInput1
SNVT_switch
nvoDigInput2
SNVT_switch
nvoDrvFault
SNVT_count
nvoGenRdData
SNVT_count
nv 12
nv 13
nv 14
nv 15
nv 16
nv 17
nv 18
nv 2
Drive
Object
Node
Object
RESOURCE FILES
The resource files can also be downloaded at: