User manual
AC Adjustable Frequency Drives
PowerFlex 700
78
Standard Drives Selection
208/240V ac, Three-Phase Drives
240V ac Input ✶ 208V ac Input IP20, NEMA Type 1
Frame
Size
Output Amps
Normal
Duty Hp
Heavy
Duty Hp
Output Amps
Normal
Duty kW
Heavy
Duty kW
Cat. No.Cont. 1 Min. 3 Sec. Cont. 1 Min. 3 Sec.
2.2 2.4 3.3 0.5 0.33 2.5 2.8 3.8 0.37 — 20BB2P2A0AYNBNC0 0
4.2 4.8 6.4 1 0.75 4.8 5.6 7 0.75 0.37 20BB4P2A0AYNBNC0 0
6.8 9 12 2 1.5 7.8 10.4 13.8 1.5 0.75
20BB6P8A0AYNBNC0 1
9.6 10.6 14.4 3 2 11 12.1 17 2.2 1.5
20BB9P6A0AYNBNC0 1
15.3 16.8 23 5 3 17.5 19.3 26.3 4 2.2
20BB015A0AYNBNC0 1
22 24.2 33 7.5 5 25.3 27.8 38 5.5 4 20BB022A0AYNBNC0 1
28 33 44 10 7.5 32.2 38 50.6 7.5 5.5
20BB028A0AYNBNC0 2
42 46.2 63 15 10 48.3 53.1 72.5 11 7.5
20BB042A0AYNBNC0 3
52 63 80 20 15 56 64 86 15 11
20BB052A0AYNBNC0 3
70 78 105 25 20 78.2 86 117.3 18.5 15 20BB070A0ANNANC0 4
80 105 136 30 25 92 117.3 156.4 22 18.5
20BB080A0ANNANC0 4
104 (80) 7
115 (120) 175 (160) 40 30 120 (92) 132 (138) 175 (175) 30 22
20BB104A0ANNANC0 5
130 (104) 7
143 (156) 175 (175) 50 40 130 (104) 143 (156) 175 (175) 37 30 20BB130A0ANNANC0 5
154 (130) 7
169 (195) 231 (260) 60 50 177 (150) 195 (225) 266 (300) 45 37 20BB154A0ANNANC0 6
192 (154) 7
211 (231) 288 (308) 75 60 221 (177) 243 (266) 308 (308) 55 45
20BB192A0ANNANC0 6
260 (205) 7
286 (305) 390 (410) 100 75 260 (205) 286 (305) 390 (410) 66 55 20BB260A0ANNANC0 6
✶ Catalog number corresponds to output amps in these columns. Drive must be programmed to lower voltage to obtain higher currents shown at right.
7 Frame 5 and 6 drives have dual current ratings; one for normal duty applications, and one for heavy duty applications (in parenthesis). The drive may be
operated at either rating.
380…480V ac, Three-Phase Drives
480V ac Input ✶ 380…400V ac Input
Cat. No.
Frame
Size
Output Amps
Normal
Duty Hp
Heavy
Duty Hp
Output Amps
Normal
Duty kW
Heavy
Duty kWCont. 1 Min. 3 Sec. Cont. 1 Min. 3 Sec.
1.1 1.2 1.6 0.5 0.33 1.3 1.4 1.9 0.37 0.25 20BD1P1A0AYNANC0 0
2.1 2.4 3.2 1 0.75 2.1 2.4 3.2 0.75 0.55 20BD2P1A0AYNANC0 0
3.4 4.5 6 2 1.5 3.5 4.5 6 1.5 0.75
20BD3P4A0AYNANC0 0
5 5.5 7.5 3 2 5 5.5 7.5 2.2 1.5 20BD5P0A0AYNANC0 0
8 8.8 12 5 3 8.7 9.9 13.2 4 2.2
20BD8P0A0AYNANC0 0
11 12.1 16.5 7.5 5 11.5 13 17.4 5.5 4 20BD011A0AYNANC0 0
14 16.5 22 10 7.5 15.4 17.2 23.1 7.5 5.5
20BD014A0AYNANC0 1
22 24.2 33 15 10 22 24.2 33 11 7.5
20BD022A0AYNANC0 1
27 33 44 20 15 30 33 45 15 11 20BD027A0AYNANC0 2
34 40.5 54 25 20 37 45 60 18.5 15
20BD034A0AYNANC0 2
40 51 68 30 25 43 56 74 22 18.5 20BD040A0AYNANC0 3
52 60 80 40 30 56 64 86 30 22 20BD052A0AYNANC0 3
65 78 104 50 40 72 84 112 37 30
20BD065A0AYNANC0 3
77 (65) 7
85 (98) 116 (130) 60 50
85 (72)
➤
94 (108) 128 (144) 45 37 20BD077A0ANNANC0 4
96 (77) 7
106 (116) 144 (154) 75 60 105 (85) 116 (128) 158 (170) 55 45 20BD096A0ANNANC0 5
125 (96) 7
138 (144) 163 (168) 100 75 125 (96) 138 (144) 163 (168) 55 45 20BD125A0ANNANC0 5
156 (125) 7
172 (188) 233 (250) 125 100 170 (140) 187 (210) 255 (280) 90 75
20BD156A0ANNANC0 6
180 (156) 7
198 (234) 270 (312) 150 125
205 (170)
220 (255) 289 (313) 110 90 20BD180A0ANNANC0 6
248 (180)
7
➤
273 (270) 372 (360) 200 150
260 (205)
➤
286 (308) 390 (410) 132 110 20BD248A0ANNANC0 6
✶ Catalog number corresponds to output amps in these columns. Drive must be programmed to lower voltage to obtain higher currents shown at right.
7 Frame 4, 5 and 6 drives have dual current ratings; one for normal duty applications, and one for heavy duty applications (in parenthesis). The drive may be
operated at either rating.
➤ Rating is limited to 45°C surrounding air.
Rating is limited to 40°C surrounding air.
Wall Mount - IP21, NEMA Type 1 (Position d = A)