User manual

AC Adjustable Frequency Drives
PowerFlex 70
59
Input and Output Line Reactors - 600V, 60 Hz, Three-Phase, 3% Impedance
Drive Cat. No. Duty Hp
Input Line Reactor 7 Output Line Reactor 7
IP00 (Open Style) IP11 (NEMA Type 1) IP00 (Open Style) IP11 (NEMA Type 1)
Cat. No. Cat. No. Cat. No. Cat. No.
20AE0P9 Heavy Duty 0.33 1321-3R1-C 1321-3RA1-C 1321-3R1-B 1321-3RA1-B
20AE0P9 Normal Duty 0.5 1321-3R1-C 1321-3RA1-C 1321-3R1-B 1321-3RA1-B
20AE1P7 Heavy Duty 0.75 1321-3R2-B 1321-3RA2-B 1321-3R2-B 1321-3RA2-B
20AE1P7 Normal Duty 1.0 1321-3R2-B 1321-3RA2-B 1321-3R2-B 1321-3RA2-B
20AE2P7 Heavy Duty 1.5 1321-3R2-A 1321-3RA2-A 1321-3R4-D 1321-3RA4-D
20AE2P7 Normal Duty 2.0 1321-3R4-C 1321-3RA4-C 1321-3R4-D 1321-3RA4-D
20AE3P9 Heavy Duty 2.0 1321-3R4-C 1321-3RA4-C 1321-3R4-C 1321-3RA4-C
20AE3P9 Normal Duty 3.0 1321-3R4-C 1321-3RA4-C 1321-3R4-C 1321-3RA4-C
20AE6P1 Heavy Duty 3.0 1321-3R4-C 1321-3RA4-C 1321-3R8-C 1321-3RA8-C
20AE6P1 Normal Duty 5.0 1321-3R8-C 1321-3RA8-C 1321-3R8-C 1321-3RA8-C
20AE9P0 Heavy Duty 5.0 1321-3R8-C 1321-3RA8-C 1321-3R12-C 1321-3RA12-C
20AE9P0 Normal Duty 7.5 1321-3R12-C 1321-3RA12-C 1321-3R12-C 1321-3RA12-C
20AE011 Heavy Duty 7.5 1321-3R12-C 1321-3RA12-C 1321-3R12-B 1321-3RA12-B
20AE011 Normal Duty 10 1321-3R12-B 1321-3RA12-B 1321-3R12-B 1321-3RA12-B
20AE017 Heavy Duty 10 1321-3R12-B 1321-3RA12-B 1321-3R18-C 1321-3RA18-C
20AE017 Normal Duty 15 1321-3R18-B 1321-3RA18-B 1321-3R18-C 1321-3RA18-C
20AE022 Heavy Duty 15 1321-3R18-B 1321-3RA18-B 1321-3R25-B 1321-3RA25-B
20AE022 Normal Duty 20 1321-3R25-B 1321-3RA25-B 1321-3R25-B 1321-3RA25-B
20AE027 Heavy Duty 20 1321-3R25-B 1321-3RA25-B 1321-3R35-C 1321-3RA35-C
20AE027 Normal Duty 25 1321-3R35-C 1321-3RA35-C 1321-3R35-C 1321-3RA35-C
20AE032 Heavy Duty 25 1321-3R35-C 1321-3RA35-C 1321-3R35-B 1321-3RA35-B
20AE032 Normal Duty 30 1321-3R35-B 1321-3RA35-B 1321-3R35-B 1321-3RA35-B
20AE041 Heavy Duty 30 1321-3R35-B 1321-3RA35-B 1321-3R45-B 1321-3RA45-B
20AE041 Normal Duty 40 1321-3R45-B 1321-3RA45-B 1321-3R45-B 1321-3RA45-B
20AE052 Heavy Duty 40 1321-3R45-B 1321-3RA45-B 1321-3R55-B 1321-3RA55-B
20AE052 Normal Duty 50 1321-3R55-B 1321-3RA55-B 1321-3R55-B 1321-3RA55-B
7 Input line reactors were sized based on the NEC fundamental motor amps. Output line reactors were sized based on the VFD rated output currents.