User manual
AC Adjustable Frequency Drives
PowerFlex 70
52
Standard Drives Selection
Flange Mount - Front Chassis = IP20, NEMA 1; Heatsink = IP66, NEMA Type 4X/12 (Position d = F)
200...240V ac, Three-Phase Drives
Output Amps Nominal Power Ratings
Flange Type without
HIM
Frame
Size
240V ac Input
✶ 208V ac Input Normal Duty Heavy Duty Cat. No.
Cont. 1 Min. 3 Sec. Cont. 1 Min. 3 Sec. kW Hp kW Hp 20A...
2.2 2.4 3.3 2.5 2.7 3.7 0.37 0.5 0.25 0.33 B2P2F0AYNNNC0 A
4.2 4.8 6.4 4.8 5.5 7.4 0.75 1.0 0.55 0.75 B4P2F0AYNNNC0 A
6.8 9.0 12 7.8 10.3 13.8 1.5 2.0 1.1 1.5
B6P8F0AYNNNC0 B
9.6 10.6 14.4 11 12.1 16.5 2.2 3.0 1.5 2.0
B9P6F0AYNNNC0 B
15.3 17.4 23.2 17.5 19.2 26.2 4.0 5.0 3.0 3.0
B015F0AYNANC0 C
22 24.2 33 25.3 27.8 37.9 5.5 7.5 4.0 5.0 B022F0AYNANC0 D
28 33 44 32.2 37.9 50.6 7.5 10 5.5 7.5
B028F0AYNANC0 D
4246.2634355.57411157.510 B042F0AYNANC0 D
54 63 84 62.1 72.4 96.6 15 20 11 15
B054F0AYNANC0 E
70 81 108 78.2 93.1 124 18.5 25 15 20 B070F0AYNANC0 E
✶ Catalog code corresponds to output amps in these columns. Drive must be programmed to lower voltage to obtain higher currents shown at right.
380...480V ac, Three-Phase Drives
Output Amps Nominal Power Ratings
Flange Type without
HIM
Frame
Size
480V ac Input
✶ 380…400V ac Input Normal Duty Heavy Duty Cat. No.
Cont. 1 Min. 3 Sec. Cont. 1 Min. 3 Sec. kW Hp kW Hp
20A...
1.1 1.2 1.6 1.3 1.4 1.9 0.37 0.5 0.25 0.33
D1P1F0AYNNNC0 A
2.1 2.4 3.2 2.1 2.4 3.2 0.75 1.0 0.55 0.75
D2P1F0AYNNNC0 A
3.4 4.5 6.0 3.5 4.5 6.0 1.5 2.0 1.1 1.5 D3P4F0AYNNNC0 A
5.0 5.5 7.5 5.0 5.5 7.5 2.2 3.0 1.5 2.0
D5P0F0AYNNNC0 B
8.0 8.8 12 8.7 9.9 13.2 4.0 5.0 3.0 3.0 D8P0F0AYNNNC0 B
11 12.1 16.5 11.5 13 17.4 5.5 7.5 4.0 5.0
D011F0AYNANC0 C
14 16.5 22 15.4 17.2 23.1 7.5 10 5.5 7.5 D014F0AYNANC0 C
2224.2332224.23311157.510
D022F0AYNANC0 D
27 33 44 30 33 45 15 20 11 15 D027F0AYNANC0 D
3440.55437456018.5251520
D034F0AYNANC0 D
40 51 68 43 56 74 22 30 18.5 25 D040F0AYNANC0 D
52 60 80 60 66 90 30 40 22 30
D052F0AYNANC0 E
65 78 104 72 90 120 37 50 30 40 D065F0AYNANC0 E
✶ Catalog code corresponds to output amps in these columns. Drive must be programmed to lower voltage to obtain higher currents shown at right.
500...600V ac, Three-Phase Drives
Output Amps Nominal Power Ratings
Flange Type without
HIM
Frame Size
600V ac Input Normal Duty Heavy Duty
Cat. No.
Cont. 1 Min. 3 Sec. kW Hp kW Hp
20A...
0.9 1.0 1.4 0.37 0.5 0.25 0.33
E0P9F0AYNNNC0 A
1.7 1.9 2.6 0.75 1.0 0.55 0.75
E1P7F0AYNNNC0 A
2.7 3.6 4.8 1.5 2.0 1.1 1.0
E2P7F0AYNNNC0 A
3.9 4.3 5.8 2.2 3.0 1.5 1.5 E3P9F0AYNNNC0 B
6.1 6.7 9.1 4.0 5.0 3.0 3.0
E6P1F0AYNNNC0 B
9.0 9.9 13.5 5.5 7.5 4.0 5.0 E9P0F0AYNNNC0 C
11 13.5 18 7.5 10 5.5 7.5
E011F0AYNNNC0 C
17 18.7 25.5 11 15 7.5 10 E017F0AYNNNC0 D
22 25.5 34 15 20 11 15
E022F0AYNNNC0 D
27 33 44 18.5 25 15 20 E027F0AYNNNC0 D
32 40.5 54 22 30 18.5 25
E032F0AYNNNC0 D
41 48 64 30 40 22 30 E041F0AYNANC0 E
52 61.5 82 37 50 30 40
E052F0AYNANC0 E