User manual
AC Adjustable Frequency Drives
PowerFlex 400
33
Product Selection
200...240V ac, Three-Phase Drives
Drive Ratings
Rating
Panel Mount Flange Mount
kW Hp
Output Current ✶
Frame Size Cat. No. Cat. No.A
2.2 3.0 12 C
IP20/UL Open Type "
22C-B012N103 22C-B012F103
3.7 5.0 17.5 C
IP20/UL Open Type "
22C-B017N103 22C-B017F103
5.5 7.5 24 C
IP20/UL Open Type "
22C-B024N103 22C-B024F103
7.5 10 33 C
IP20/UL Open Type "
22C-B033N103 22C-B033F103
11 15 49 D IP30/NEMA 1/UL Type 1
22C-B049A103 –
15 20 65 D IP30/NEMA 1/UL Type 1
22C-B065A103 –
18.5 25 75 D IP30/NEMA 1/UL Type 1 22C-B075A103 –
22 30 90 D IP30/NEMA 1/UL Type 1
22C-B090A103 –
30 40 120 E IP30/NEMA 1/UL Type 1 22C-B120A103 –
37 50 145 E IP30/NEMA 1/UL Type 1
22C-B145A103 –
✶ Drive terminals are sized according to UL. Depending on operating ambient and wire used, some local or national codes may require a larger wire size than
what the power terminals can accept. Multiple conductors, 90°C wire, and/or lugs may be required. Refer to the PowerFlex 400 User Manual for details on
terminal block wire ranges.
" IP30/NEMA 1/UL Type 1 can be achieved for panel mount drives with top cover and optional conduit box kit installed. Field installed conversion kit specified
under User Installed Options.
380...480V ac, Three-Phase Drives
Drive Ratings
Rating
Panel Mount Flange Mount
kW Hp
Output Current
✶
Frame Size Cat. No. Cat. No.A
2.2 3.0 6.0 C
IP20/UL Open Type "
22C-D6P0N103 22C-D6P0F103
4.0 5.0 10.5 C
IP20/UL Open Type "
22C-D010N103 22C-D010F103
5.5 7.5 12 C
IP20/UL Open Type "
22C-D012N103 22C-D012F103
7.5 10 17 C
IP20/UL Open Type "
22C-D017N103 22C-D017F103
11 15 22 C
IP20/UL Open Type "
22C-D022N103 22C-D022F103 ‡
15 20 30 C
IP20/UL Open Type "
22C-D030N103 22C-D030F103 ‡
18.5 25 38 D IP30/NEMA 1/UL Type 1
22C-D038A103 –
22 30 45.5 D IP30/NEMA 1/UL Type 1
22C-D045A103 –
30 40 60 D IP30/NEMA 1/UL Type 1 22C-D060A103 –
37 50 72 E IP30/NEMA 1/UL Type 1
22C-D072A103 –
45 60 88 E IP30/NEMA 1/UL Type 1 22C-D088A103 –
55 75 105 E IP30/NEMA 1/UL Type 1
22C-D105A103 –
75 100 142 E IP30/NEMA 1/UL Type 1 22C-D142A103 –
90 125 170 F IP30/NEMA 1/UL Type 1
22C-D170A103 –
110 150 208 F IP30/NEMA 1/UL Type 1 22C-D208A103 –
✶ Drive terminals are sized according to UL. Depending on operating ambient and wire used, some local or national codes may require a larger wire size than
what the power terminals can accept. Multiple conductors, 90°C wire, and/or lugs may be required. Refer to the PowerFlex 400 User Manual for details on
terminal block wire ranges.
" IP30/NEMA 1/UL Type 1 can be achieved for panel mount drives with top cover and optional conduit box kit installed. Field installed conversion kit specified
under User Installed Options.
‡ 11 and 15 kW (15 and 20 Hp) Frame C flange mount drives require external DC series bus inductor.