User manual

AC Adjustable Frequency Drives
PowerFlex 400
33
Product Selection
200...240V ac, Three-Phase Drives
Drive Ratings
Rating
Panel Mount Flange Mount
kW Hp
Output Current
Frame Size Cat. No. Cat. No.A
2.2 3.0 12 C
IP20/UL Open Type "
22C-B012N103 22C-B012F103
3.7 5.0 17.5 C
IP20/UL Open Type "
22C-B017N103 22C-B017F103
5.5 7.5 24 C
IP20/UL Open Type "
22C-B024N103 22C-B024F103
7.5 10 33 C
IP20/UL Open Type "
22C-B033N103 22C-B033F103
11 15 49 D IP30/NEMA 1/UL Type 1
22C-B049A103
15 20 65 D IP30/NEMA 1/UL Type 1
22C-B065A103
18.5 25 75 D IP30/NEMA 1/UL Type 1 22C-B075A103
22 30 90 D IP30/NEMA 1/UL Type 1
22C-B090A103
30 40 120 E IP30/NEMA 1/UL Type 1 22C-B120A103
37 50 145 E IP30/NEMA 1/UL Type 1
22C-B145A103
Drive terminals are sized according to UL. Depending on operating ambient and wire used, some local or national codes may require a larger wire size than
what the power terminals can accept. Multiple conductors, 90°C wire, and/or lugs may be required. Refer to the PowerFlex 400 User Manual for details on
terminal block wire ranges.
" IP30/NEMA 1/UL Type 1 can be achieved for panel mount drives with top cover and optional conduit box kit installed. Field installed conversion kit specified
under User Installed Options.
380...480V ac, Three-Phase Drives
Drive Ratings
Rating
Panel Mount Flange Mount
kW Hp
Output Current
Frame Size Cat. No. Cat. No.A
2.2 3.0 6.0 C
IP20/UL Open Type "
22C-D6P0N103 22C-D6P0F103
4.0 5.0 10.5 C
IP20/UL Open Type "
22C-D010N103 22C-D010F103
5.5 7.5 12 C
IP20/UL Open Type "
22C-D012N103 22C-D012F103
7.5 10 17 C
IP20/UL Open Type "
22C-D017N103 22C-D017F103
11 15 22 C
IP20/UL Open Type "
22C-D022N103 22C-D022F103
15 20 30 C
IP20/UL Open Type "
22C-D030N103 22C-D030F103
18.5 25 38 D IP30/NEMA 1/UL Type 1
22C-D038A103
22 30 45.5 D IP30/NEMA 1/UL Type 1
22C-D045A103
30 40 60 D IP30/NEMA 1/UL Type 1 22C-D060A103
37 50 72 E IP30/NEMA 1/UL Type 1
22C-D072A103
45 60 88 E IP30/NEMA 1/UL Type 1 22C-D088A103
55 75 105 E IP30/NEMA 1/UL Type 1
22C-D105A103
75 100 142 E IP30/NEMA 1/UL Type 1 22C-D142A103
90 125 170 F IP30/NEMA 1/UL Type 1
22C-D170A103
110 150 208 F IP30/NEMA 1/UL Type 1 22C-D208A103
Drive terminals are sized according to UL. Depending on operating ambient and wire used, some local or national codes may require a larger wire size than
what the power terminals can accept. Multiple conductors, 90°C wire, and/or lugs may be required. Refer to the PowerFlex 400 User Manual for details on
terminal block wire ranges.
" IP30/NEMA 1/UL Type 1 can be achieved for panel mount drives with top cover and optional conduit box kit installed. Field installed conversion kit specified
under User Installed Options.
11 and 15 kW (15 and 20 Hp) Frame C flange mount drives require external DC series bus inductor.