User manual

AC Adjustable Frequency Drives
PowerFlex 700S
133
Phase I Product Selection
208/240V ac, Three-Phase Drives
240V ac Input 208V ac Input IP20, NEMA Type 1
Frame
Size
Output Amps
Normal
Duty Hp
Heavy Duty
Hp
Output Amps
Normal
Duty kW
Heavy Duty
kW
Cat. No.
Cont. 1 Min. 3 Sec. Cont. 1 Min. 3 Sec.
20D…
4.2 4.8 6.4 1.0 0.75 4.8 5.6 7.0 0.75 0.37
B4P2A0EYNANNNN 1
6.8 9.0 12 2.0 1.5 7.8 10.4 13.8 1.5 0.75
B6P8A0EYNANNNN 1
9.6 10.6 14.4 3.0 2.0 11 12.1 17 2.2 1.5
B9P6A0EYNANNNN 1
15.3 16.8 23 5.0 3.0 17.5 19.3 26.3 4.0 2.2
B015A0EYNANNNN 1
22 24.2 33 7.5 5.0 25.3 27.8 38 5.5 4.0
B022A0EYNANNNN 1
28 33 44 10 7.5 32.2 38 50.6 7.5 5.5
B028A0EYNANNNN 2
42 46.2 63 15 10 48.3 53.1 72.5 11 7.5
B042A0EYNANNNN 3
52 63 80 20 15 56 64 86 15 11
B052A0EYNANNNN 3
70 78 105 25 20 78.2 86 117.3 18.5 15
B070A0ENNANNNN 4
80 105 136 30 25 92 117.3 156.4 22 18.5
B080A0ENNANNNN 4
104 (80) 7
115 (120) 175 (160) 40 30 120 (92) 132 (138) 175 (175) 30 22
B104A0ENNANNNN 5
130 (104) 7
143 (156) 175 (175) 50 40 130 (104) 143 (156) 175 (175) 30 30 B130A0ENNANNNN 5
154 (130) 7
169 (195) 231 (260) 60 50 177 (150) 195 (225) 266 (300) 45 37 B154A0ENNANNNN 6
192 (154) 7
211 (231) 288 (308) 75 60 221 (177) 243 (266) 308 (308) 55 45
B192A0ENNANNNN 6
Catalog number corresponds to output amps in this column. Drive must be programmed to lower voltage to obtain higher currents shown at right.
7 These drives have dual current ratings; one for normal duty applications, and one for heavy duty applications (in parenthesis). The drive may be operated at
either rating.
380…480V ac, Three-Phase Drives
480V ac Input 380…400V ac Input IP20, NEMA Type 1
Frame
Size
Output Amps
Normal
Duty Hp
Heavy
Duty Hp
Output Amps
Normal
Duty kW
Heavy
Duty kW
Cat. No.
Cont. 1 Min. 3 Sec. Cont. 1 Min. 3 Sec.
20D…
2.1 2.4 3.2 1 0.75 2.1 2.4 3.2 0.75 0.55
D2P1A0EYNANNNN 1
3.4 4.5 6 2 1.5 3.5 4.5 6 1.5 0.75
D3P4A0EYNANNNN 1
5 5.5 7.5 3 2 5 5.5 7.5 2.2 1.5
D5P0A0EYNANNNN 1
8 8.8 12 5 3 8.7 9.9 13.2 4 2.2
D8P0A0EYNANNNN 1
11 12.1 16.5 7.5 5 11.5 13 17.4 5.5 4
D011A0EYNANNNN 1
14 16.5 22 10 7.5 15.4 17.2 23.1 7.5 5.5
D014A0EYNANNNN 1
22 24.2 33 15 10 22 24.2 33 11 7.5
D022A0EYNANNNN 1
27 33 44 20 15 30 33 45 15 11
D027A0EYNANNNN 2
34 40.5 54 25 20 37 45 60 18.5 15
D034A0EYNANNNN 2
40 51 68 30 25 43 56 74 22 18.5
D040A0EYNANNNN 3
52 60 80 40 30 56 64 86 30 22
D052A0EYNANNNN 3
65 78 104 50 40 72 84 112 37 30
D065A0EYNANNNN 3
77 (65) 7
85 (98) 116 (130) 60 50 85 (72) 94 (108) 128 (144) 45 37
D077A0ENNANNNN 4
96 (77) 7
106 (116) 144 (154) 75 60 105 (85) 116 (128) 158 (170) 55 45 D096 A0ENNANNNN 5
125 (96) 7
138 (144) 163 (168) 100 75 125 (96) 138 (144) 163 (168) 55 45
D125A0ENNANNNN 5
156 (125) 7
172 (188) 233 (250) 125 100 170 (140) 187 (210) 255 (280) 90 75 D156A0ENNANNNN 6
180 (156) 7
198 (234) 270 (312) 150 125 205 (170) § 220 (255) 289 (313) 110 90
D180A0ENNANNNN 6
248 (180) 7
273 (270) 372 (360) 200 150 260 (205) 286 (308) 390 (410) 132 110 D248A0ENNANNNN 6
261 (205) 7
287 (308) 410 (410) 200 150 261 (205) 287 (308) 410 (410) 132 110
D261A0ENNBNNNN
9
300 (245) 7
330 (368) 450 (490) 250 200 300 (245) 330 (368) 450 (490) 160 132
D300A0ENNBNNNN
9
385 (300) 7
424 (450) 600 (600) 300 250 385 (300) 424 (450) 600 (600) 200 160
D385A0ENNBNNNN
10
460 (385) 7
506 (578) 770 (770) 350 300 460 (385) 506 (578) 770 (770) 250 200
D460A0ENNBNNNN
10
500 (420) 7
550 (630) 750 (840) 450 350 500 (420) 550 (630) 750 (840) 250 200
D500A0ENNBNNNN
10
590 (520) 7
649 (780) 1040 (1040) 500 450 590 (520) 649 (780) 1040 (1040) 315 250
D590A0ENNBNNNN
11
650 (590) 7
715 (885) 1180 (1180) 500 500 650 (590) 715 (885) 1180 (1180) 355 315
D650A0ENNBNNNN
11
730 (650) 7
803 (945) 1095 (1260) 600 500 730 (650) 803 (945) 1095 (1260) 400 355
D730A0ENNBNNNN
11
Catalog number corresponds to output amps in this column. Drive must be programmed to lower voltage to obtain higher currents shown at right.
7 These have dual current ratings; one for normal duty applications, and one for heavy duty (in parenthesis). The drive may be operated at either rating.
380-400V, 85 A rating is limited to 45°C surrounding air.
§ 380-400V, 205 A rating is limited to 40°C surrounding air.
Rating is limited to 40°C surrounding air.