User manual
AC Adjustable Frequency Drives
PowerFlex 700S
130
Flange Mount
Front = IP20, NEMA Type Open, Back/Heatsink = IP54, NEMA Type 12 (Position d = F)
Phase I PowerFlex 700S
Phase I Control
Phase I Features
Digital Inputs
(4) 24V dc Inputs
(3) Programmable
(1) Enable Inputs
Digital Outputs
(2) Open Collector, Max Load 25 mA
(1) Relay, 24V dc
Analog Inputs (2) ±10V dc/±1V dc Differential Inputs, 13 bit + sign
Analog Outputs (2) ±10V dc Differential Outputs, 11 bit + sign
Encoder Inputs (2) 5/12V Encoder Inputs Quadrature/Differential
DriveLogix - I/O
Option
Flex I/O - up to 1 rail, (8) modules
380…480V ac, Three-Phase Drives
480V ac Input ✶ 380…400V ac Input
Cat. No.
Frame
Size
Output Amps
Normal
Duty Hp
Heavy
Duty Hp
Output Amps
Normal
Duty kW
Heavy
Duty kWCont. 1 Min. 3 Sec. Cont. 1 Min. 3 Sec.
20D…
96 (77) 7
106 (116) 144 (154) 75 60 105 (85) 116 (128) 158 (170) 55 45
D096F0ENNANANE 5
125 (96) 7
138 (144) 163 (168) 100 75 125 (96) 138 (144) 163 (168) 55 45 D125F0ENNANANE 5
156 (125) 7
172 (188) 233 (250) 125 100 170 (140) 187 (210) 255 (280) 90 75 D156F0ENNANANE 6
180 (156) 7
198 (234) 270 (312) 150 125
205 (170)
220 (255) 289 (313) 110 90
D180F0ENNANANE 6
248 (180)
7
➤
273 (270) 372 (360) 200 150
260 (205)
➤
286 (308) 390 (410) 132 110 D248F0ENNANANE 6
✶ Catalog number corresponds to output amps in these columns. Drive must be programmed to lower voltage to obtain higher currents shown at right.
7 Frame 5 and 6 drives have dual current ratings; one for normal duty applications, and one for heavy duty applications (in parenthesis). The drive may be
operated at either rating.
➤ Rating is limited to 45°C surrounding air.
Rating is limited to 40°C surrounding air.