User manual
AC Adjustable Frequency Drives
PowerFlex 700S
127
380…480V ac, Three-Phase Drives
480V ac Input ✶ 380…400V ac Input IP20, NEMA Type 1
Frame
Size
Output Amps
Normal
Duty Hp
Heavy
Duty Hp
Output Amps
Normal
Duty kW
Heavy
Duty kW
Cat. No.
Cont. 1 Min. 3 Sec. Cont. 1 Min. 3 Sec.
20D…
2.1 2.4 3.2 1 0.75 2.1 2.4 3.2 0.75 0.55
D2P1A0EYNANANE 1
3.4 4.5 6 2 1.5 3.5 4.5 6 1.5 0.75
D3P4A0EYNANANE 1
5 5.5 7.5 3 2 5 5.5 7.5 2.2 1.5
D5P0A0EYNANANE 1
8 8.8 12 5 3 8.7 9.9 13.2 4 2.2
D8P0A0EYNANANE 1
11 12.1 16.5 7.5 5 11.5 13 17.4 5.5 4
D011A0EYNANANE 1
14 16.5 22 10 7.5 15.4 17.2 23.1 7.5 5.5
D014A0EYNANANE 1
22 24.2 33 15 10 22 24.2 33 11 7.5
D022A0EYNANANE 1
27 33 44 20 15 30 33 45 15 11
D027A0EYNANANE 2
34 40.5 54 25 20 37 45 60 18.5 15
D034A0EYNANANE 2
40 51 68 30 25 43 56 74 22 18.5
D040A0EYNANANE 3
52 60 80 40 30 56 64 86 30 22
D052A0EYNANANE 3
65 78 104 50 40 72 84 112 37 30
D065A0EYNANANE 3
77 (65) 7
85 (98) 116 (130) 60 50 85 (72) ‡ 94 (108) 128 (144) 45 37
D077A0ENNANANE 4
96 (77) 7
106 (116) 144 (154) 75 60 105 (85) 116 (128) 158 (170) 55 45 D096A0ENNANANE 5
125 (96) 7
138 (144) 163 (168) 100 75 125 (96) 138 (144) 163 (168) 55 45
D125A0ENNANANE 5
156 (125) 7
172 (188) 233 (250) 125 100 170 (140) 187 (210) 255 (280) 90 75 D156A0ENNANANE 6
180 (156) 7
198 (234) 270 (312) 150 125 205 (170) § 220 (255) 289 (313) 110 90 D180A0ENNANANE 6
248 (180) 7
273 (270) 372 (360) 200 150 260 (205) 286 (308) 390 (410) 132 110
D248A0ENNANANE 6
261 (205) 7
287 (308) 410 (410) 200 150 261 (205) 287 (308) 410 (410) 132 110 D261A0ENNBNANE 9
300 (245) 7
330 (368) 450 (490) 250 200 300 (245) 330 (368) 450 (490) 160 130 D300A0ENNBNANE 9
385 (300) 7
424 (450) 600 (600) 300 250 385 (300) 424 (450) 600 (600) 200 160
D385A0ENNBNANE 10
460 (385) 7
506 (578) 770 (770) 350 300 460 (385) 506 (578) 770 (770) 250 200 D460A0ENNBNANE 10
500 (420) 7
550 (630) 750 (840) 450 350 500 (420) 550 (630) 750 (840) 250 250 D500A0ENNBNANE 10
590 (520) 7
649 (780) 956 (956) 500 450 590 (520) 649 (780) 956 (956) 315 250
D590A0ENNBNANE 11
650 (590) 7
715 (885)
1062
(1062)
500 500 650 (590) 715 (885)
1062
(1062)
355 315
D650A0ENNBNANE 11
730 (650) 7
803 (975)
1095
(1170)
600 500 730 (650) 803 (975)
1095
(1170)
400 355
D730A0ENNBNANE 11
820 (730)
7♠
902 (1095)
1230
(1314)
700 600 820 (730) 902 (1095)
1230
(1314)
450 400
D820A0ENNBNANE 12
920 (820)
7♠
1012
(1230)
1380
(1476)
800 700 920 (820)
1012
(1230)
1380
(1476)
500 450
D920A0ENNBNANE 12
1030 (920)
7a♠
1133
(1370)
1555
(1600)
900 800 1030 (920)
1133
(1370)
1555
(1600)
560 500
D1K0A0ENNBNANE 12
✶ Catalog number corresponds to output amps in this column. Drive must be programmed to lower voltage to obtain higher currents shown at right.
7 These drives have dual current ratings; one for normal duty applications, and one for heavy duty (in parenthesis). The drive may be operated at either rating.
‡ 380-400V, 85 A rating is limited to 45°C surrounding air.
§ 380-400V, 205 A rating is limited to 40°C surrounding air.
a Rating is limited to 35°C surrounding air.
♠ Release pending at date of printing. Verify before ordering.