User manual

AC Adjustable Frequency Drives
PowerFlex 4
11
Input Line Reactors - 240V, 50/60 Hz, Three-Phase, 3% Impedance
kW Hp
Fundamental Amps
Maximum
Continuous Amps Inductance Watts Loss
Cat. No.AAmhW
0.2 0.25 2.0 3.0 12 7.5 1321-3R2-A
0.4 0.5 4.0 6.0 12 21 1321-3R4-B
0.75 1.0 8.0 12 3.0 29
1321-3R8-B
1.5 2.0 8.0 12 1.5 19.5 1321-3R8-A
2.2 3.0 12 18 1.25 26
1321-3R12-A
3.7 5.0 18 27 0.8 36 1321-3R18-A
Catalog numbers listed are for 3% impedance open style units. NEMA Type 1 and 5% impedance reactor types are also available. Refer to publication 1321-
TD001….
Input Line Reactors - 480V, 50/60 Hz, Three-Phase, 3% Impedance
kW Hp
Fundamental Amps
Maximum
Continuous Amps Inductance Watts Loss
Cat. No.AAmhW
0.4 0.5 2.0 3.0 20 11.3
1321-3R2-B
0.75 1.0 4.0 6.0 9.0 20
1321-3R4-C
1.5 2.0 4.0 6.0 6.5 20 1321-3R4-B
2.2 3.0 8.0 12 5.0 25.3
1321-3R8-C
3.7 5.0 8.0 12 3.0 29 1321-3R8-B
Catalog numbers listed are for 3% impedance open style units. NEMA Type 1 and 5% impedance reactor types are also available. Refer to publication 1321-
TD001….
EMC Filters
Drive Ratings S Type Filter L Type Filter
Input Voltage kW Hp
Cat. No. Cat. No.
120V 50/60 Hz
1-Phase
0.2 0.25
22-RF010-AL
0.4 0.5 22-RF010-AL
0.75 1.0
22-RF018-BL
1.1 1.5 22-RF025-CL §
240V 50/60 Hz
1-Phase
0.2 0.25
"
22-RF010-AL
0.4 0.5
"
22-RF010-AL
0.75 1.0
"
22-RF010-AL
1.5 2.0
"
22-RF018-BL
240V 50/60 Hz
1-Phase
NO BRAKE
0.2 0.25
"
22-RF010-AL
0.4 0.5
"
22-RF010-AL
0.75 1.0
"
22-RF010-AL
1.5 2.0
"
22-RF018-BL
2.2 3.0
"
22-RF025-CL §
240V 50/60 Hz
3-Phase
0.2 0.25
22-RF9P5-AS 22-RF9P5-AL
0.4 0.5 22-RF9P5-AS 22-RF9P5-AL
0.75 1.0
22-RF9P5-AS 22-RF9P5-AL
1.5 2.0
22-RF9P5-AS 22-RF9P5-AL
2.2 3.0 22-RF021-BS 22-RF021-BL
3.7 5.0 22-RF021-BS 22-RF021-BL
480V 50/60 Hz
3-Phase
0.4 0.5
22-RF5P7-AS 22-RF5P7-AL
0.75 1.0 22-RF5P7-AS 22-RF5P7-AL
1.5 2.0
22-RF5P7-AS 22-RF5P7-AL
2.2 3.0 22-RF012-BS 22-RF012-BL
3.7 5.0
22-RF012-BS 22-RF012-BL
This filter is suitable for use with a cable length of up to 10 meters for Class A and 1 meter for Class B environments.
" Drives are available in these ratings with internal “S Type” filters.
This filter is suitable for use with a cable length of up to 100 meters for Class A and 5 meters for Class B environments.
§ The piggyback mounting option cannot be used with Frame B PowerFlex 4 drives and Frame C EMC Line Filters.