User manual
AC Adjustable Frequency Drives
PowerFlex 700H
117
Product Selection
380…500V ac, Three-Phase Drives
480V ac Input 380…400V ac Input IP21, NEMA Type 1
Frame
Size
Output Amps Normal
Duty
Hp
Heavy
Duty
Hp
Output Amps Normal
Duty
kW
Heavy
Duty
kW
Cat No.
Cont.
✶ 1 Min.
2 Sec. 7
Cont. 1 Min.
2 Sec. 7
20CD …(480V)
261 (205) 287 (308) 349 (349) 200 150 261 (205) 287 (308) 349 (349) 132 110
261A0ANNBNN0 9
300 (245) 330 (368) 444 (444) 250 200 300 (245) 330 (368) 444 (444) 160 132
300A0ANNBNN0 9
385 (300) 424 (450) 540 (540) 300 250 385 (300) 424 (450) 540 (540) 200 160 385A0ANNBNN0 10
460 (385) 506 (578) 693 (693) 350 300 460 (385) 506 (578) 693 (693) 250 200
460A0ANNBNN0 10
500 (420) 550 (630) 828 (828) 450 350 500 (420) 550 (630) 828 (828) 250 250 500A0ANNBNN0 10
590 (520) 649 (780) 956 (956) 500 450 590 (520) 649 (780) 956 (956) 315 250
590A0ANNBNN0 11
650 (590) 715 (885) 1062 (1062) 500 500 650 (590) 715 (885) 1062 (1062) 355 315
650A0ANNBNN0 11
730 (650) 803 (975) 1095 (1170) 600 500 730 (650) 803 (975) 1095 (1170) 400 355
730A0ANNBNN0 11
820 (730) 902 (1095) 1230 (1314) 700 600 820 (730) 902 (1095) 1230 (1314) 450 400 820A0ANNBNN0 12
920 (820) 1012 (1230) 1380 (1476) 800 700 920 (820) 1012 (1230) 1380 (1476) 500 450
920A0ANNBNN0 12
1030 (920)‡ 1133 (1370) 1555 (1600) 900 800 1030 (920)‡ 1133 (1370) 1555 (1600) 560 500
1K0A0ANNBNN0 12
✶ These drives have dual current ratings; one for normal duty applications, and one for heavy duty applications (in parenthesis). The drive may be operated at
either rating.
7 The 2 sec. output current is only available at initial start or drive operating at light load.
‡ Heavy duty rating is limited to 35° C surrounding air.
600…690V ac, Three-Phase Drives
600V ac Input 690V ac Input IP21, NEMA Type 1
Frame Size
Output Amps
Normal
Duty Hp
Heavy
Duty Hp
Output Amps
Normal
Duty kW
Heavy
Duty kW
Cat. No.
Cont. ✶ 1 Min.
2 Sec. 7
Cont. ✶ 1 Min.
2 Sec. 7
20CE …(600V)
170 (144) 187 (216) 245 (245) 150 150 170 (144) 187 (216) 245 (245) 160 132 170A0ANNBNN0 9
208 (170) 230 (250) 289 (289) 200 150 208 (170) 230 (250) 289 (289) 200 160 208A0ANNBNN0 9
261 (208) 287 (312) 375 (375) 250 200 261 (208) 287 (312) 375 (375) 250 200
261A0ANNBNN0 10
325 (261) 358 (392) 470 (470) 350 250 325 (261) 358 (392) 470 (470) 315 250 325A0ANNBNN0 10
385 (325) 424 (488) 585 (585) 400 350 385 (325) 424 (488) 585 (585) 355 315
385A0ANNBNN0 10
416 (325)‡ 458 (488) 585 (585) 450 350 416 (325)‡ 458 (488) 585 (585) 400 315 416A0ANNBNN0 10
460 (385) 506 (578) 693 (693) 450 400 460 (385) 506 (578) 693 (693) 450 355
460A0ANNBNN0 11
502 (460) 552 (690) 828 (828) 500 450 502 (460) 552 (690) 828 (828) 500 450
502A0ANNBNN0 11
590 (502) 649 (753) 904 (904) 600 500 590 (502) 649 (753) 904 (904) 560 500 590A0ANNBNN0 11
650 (590) 715 (885) 1062 (1062) 700 650 650 (590) 715 (885) 1062 (1062) 630 560
650A0ANNBNN0 12
750 (650) 825 (975) 1170 (1170) 800 700 750 (650) 825 (975) 1170 (1170) 710 630 750A0ANNBNN0 12
820 (750)‡ 902 (975) 1170 (1170) 900 700 820 (750)‡ 902 (975) 1170 (1170) 800 630
820A0ANNBNN0 12
✶ These drives have dual current ratings; one for normal duty applications, and one for heavy duty applications (in parenthesis). The drive may be operated at
either rating.
7 The 2 sec. output current is only available at initial start or drive operating at light load.
‡ Normal duty rating is limited to 35° C surrounding air.