User manual

AC Adjustable Frequency Drives
PowerFlex Drive Packages for Fan & Pump Applications
112
Input and Output Line Reactors (Standalone)
208V, 60 Hz, Three-Phase
Drive Ratings
Input Line Reactor Output Line Reactor
IP00 (Open Style) IP11 (NEMA Type 1) IP00 (Open Style) IP11 (NEMA Type 1)
kW Hp Amps Cat. No. Cat. No. Cat. No. Cat. No.
3% Impedance
0.75 1.0 4.8 1321-3R8-B 1321-3RA8-B 1321-3R8-B 1321-3RA8-B
1.5 2.0 7.8
1321-3R8-A 1321-3RA8-A 1321-3R8-A 1321-3RA8-A
2.2 3.0 11 1321-3R12-A 1321-3RA12-A 1321-3R12-A 1321-3RA12-A
4.0 5.0 17.5
1321-3R18-A 1321-3RA18-A 1321-3R18-A 1321-3RA18-A
5.5 7.5 25.3
1321-3R25-A 1321-3RA25-A 1321-3R25-A 1321-3RA25-A
7.5 10 32.2 1321-3R35-A 1321-3RA35-A 1321-3R35-A 1321-3RA35-A
11 15 43
1321-3R45-A 1321-3RA45-A 1321-3R45-A 1321-3RA45-A
5% Impedance
0.75 1.0 4.8
1321-3R8-C 1321-3RA8-C 1321-3R8-B 1321-3RA8-B
1.5 2.0 7.8 1321-3R8-B 1321-3RA8-B 1321-3R8-B 1321-3RA8-B
2.2 3.0 11
1321-3R12-B 1321-3RA12-B 1321-3R12-B 1321-3RA12-B
4.0 5.0 17.5 1321-3R18-B 1321-3RA18-B 1321-3R18-B 1321-3RA18-B
5.5 7.5 25.3
1321-3R25-B 1321-3RA25-B 1321-3R25-B 1321-3RA25-B
7.5 10 32.2 1321-3R35-B 1321-3RA35-B 1321-3R35-B 1321-3RA35-B
11 15 43
1321-3R45-B 1321-3RA45-B 1321-3R45-B 1321-3RA45-B
Input line reactors were sized based on the NEC fundamental motor amps. Output line reactors were sized based on the VFD rating output currents.