AC Adjustable Frequency Drives
PowerFlex 700
99
Packaged Drives Programs
Power Disconnecting Means
Important: Customer must select one of the following; -P1, P2,
P3, P4, P6 or -P7. If option -P1 is selected, power disconnecting
means and drive branch circuit protection must be supplied by
user.
Power and Bypass Options
Control Power and Line Reactor Options
Technical Information for Thermal Overload Relays
Class 10 (Bulletin 193) Relays:
y Will trip in 10 seconds or less at 600% of device current rating.
y Trip setting is adjustable per the range chart shown.
y Range is chosen to cover maximum drive current rating.
y If a motor outside the published adjustability range is to be used
- enter customer order and provide complete motor data.
480V AC, Three-Phase Drives
Drive Rating ND
Hp
Drive Rating HD
Hp
Class 10 Adjustable Thermal
Overload Relay - Electronic
Adjustable Range (Amps)
Normal Duty Heavy Duty
0.5 0.33 1.0-2.9 0.32-1.0
1 0.75 1.0-2.9 1.0-2.9
2 1.5 1.6-5.0 1.6-5.0
3 2 1.6-5.0 1.6-5.0
5 3 3.7-12 1.6-5.0
7.5 5 3.7-12 3.7-12
10 7.5 12-32 3.7-12
15 10 13-37 13-37
20 15 13-37 13-37
25 20 13-37 13-37
30 25 14-45 14-45
40 30 26-85 26-85
50 40 26-85 26-85
60 50 26-85 26-85
75 60 66-110 26-85
100 75 57-180 66-110
125 100 57-180 57-180
150 125 57-180 57-180
200 150 96-300 57-180
240V AC, Three-Phase Drives
Drive Rating ND
Hp
Drive Rating HD
Hp
Class 10 Adjustable Thermal
Overload Relay - Electronic
Adjustable Range (Amps)
Normal Duty Heavy Duty
Engineered Drives Program Only
0.5 0.33 1.0-2.9 1.0-2.9
1 0.75 1.6-5.0 1.6-5.0
2 1.5 3.7-12 3.7-12
3 2 3.7-12 3.7-12
5 3 12-32 3.7-12
7.5 5 12-32 12-32
10 7.5 13-37 13-37
15 10 14-45 14-45
20 15 26-85 26-85
25 20 – –
30 25 – –
40 30 – –
50 40 – –
60 50 – –
75 60 – –
100 75 – –
125 100 – –
150 125 – –
Description Option Code
No Input Protection
-P1
Drive Input Fuses
-P2 ✶
Drive Circuit Breaker
-P3 ✶
Drive Bypass Mode, Circuit Breaker
-P4 7
Drive Disconnect Switch, Fused
-P6 ✶
Drive Bypass Mode, Fused Disconnect
-P7 7
✶ This option can not be used with Bypass.
7 This option must be used in conjunction with a Bypass Option.
Description Option Code
115V Control Power, Drive/Options Only
-C1
115V Control Power, User Supplied
-C5
3% Line Reactor Mounted in Enclosure
Input
-L1
Output
-L2
Option -C1 or -C5 must be selected.
Description Option Code
Contactor, Drive Input
-P11 ‡a
Contactor, Drive Output
-P12 ‡§a
No Bypass Required
-B0
Manual Bypass
-B1 ♣a
Automatic Bypass
-B2 ♣➤
‡ Either an input contactor or output contactor may be chosen, but not
both when Bypass is selected.
§ This option must be used in conjunction with the Auxiliary Fault Contact
option -J2.
♣ Includes a Class 10 Adjustable Thermal Overload Relay that does not
require separate heater elements.
➤ This option includes “Drive-Off-Bypass” selector switch and must be used
in conjunction with the Auxiliary Fault Contact option (-J2). Also requires
option -B1.
a Requires option -C1 or user supplied 115V (option -C5).
B0 or B1 must be selected.