Owner's manual

I-2 Logic Command/Status Words
Logic Status Word
*PowerFlex 40 only
PowerFlex 4 and PowerFlex 40 Drives
Logic Bits
15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0 Status Description
x Ready 0 = Not Ready
1 = Ready
x Active 0 = Not Active
1 = Active
x Command
Direction
0 = Reverse
1 = Forward
xActual
Direction
0 = Reverse
1 = Forward
x Accel 0 = Not Accelerating
1 = Accelerating
x Decel 0 = Not Decelerating
1 = Decelerating
x Alarm 0 = No Alarm
1 = Alarm
x Fault 0 = No Fault
1 = Fault
x At Speed 0 = Not At Reference
1 = At Reference
x Main Freq 0 = Not Controlled By Comm
1 = Controlled By Comm
x Operation
Command
0 = Not Controlled By Comm
1 = Controlled By Comm
x Parameters 0 = Not Locked
1 = Locked
xDigital
Input 1
Status
0 = Open
1 = Closed
xDigital
Input 2
Status
0 = Open
1 = Closed
xDigital
Input 3 *
Status
0 = Open
1 = Closed
xDigital
Input 4 *
Status
0 = Open
1 = Closed