Owner's manual

B-2 Serial Converter Module Parameters
No. Name and Description Details
05 [Reset Module]
No action if set to “Ready.” Resets the serial converter
module if set to “Reset Module.” Restores the module
to its factory-default settings if set to “Set Defaults.
This parameter is a command. It will be reset to “0 =
Ready” after the command has been performed.
Default: 0 = Ready
Values: 0 = Ready
1 = Reset Module
2 = Set Defaults
Type: Read/Write
06 [Clear DF1 Counts]
No action if set to “Ready.Resets the DF1 statistical
parameters (numbers 07 – 15) to 0 if set to “Clear
Counts.” This parameter is a command. It will be reset
to “0 = Ready” after the command has been
performed.
Default: 0 = Ready
Values: 0 = Ready
1 = Clear Counts
Type: Read/Write
Reset Required: No
07 [DF1 Packets Sent]
Displays the number of DF1 packets sent by the serial
converter module. The value of this parameter is
normally approximately equal to the value of
Parameter 08 - [DF1 Packets Rcvd].
Default: 0
Minimum: 0
Maximum: 4294967295
Type: Read Only
08 [DF1 Packets Rcvd]
Displays the number of DF1 packets received by the
serial converter module. The value of this parameter is
normally approximately equal to the value of
Parameter 07 - [DF1 Packets Sent].
Default: 0
Minimum: 0
Maximum: 4294967295
Type: Read Only
09 [Undelivered Msgs]
(1)
Displays the number of DF1 messages that were sent
but not acknowledged.
Default: 0
Minimum: 0
Maximum: 65535
Type: Read Only
10 [ENQs Sent]
(1)
Displays the number of ENQ characters sent by the
serial converter module.
Default: 0
Minimum: 0
Maximum: 65535
Type: Read Only
11 [ENQs Received]
(1)
Displays the number of ENQ characters received by
the serial converter module.
Default: 0
Minimum: 0
Maximum: 65535
Type: Read Only
12 [NAKs Received]
(1)
Displays the number of NAK characters received by
the serial converter module.
Default: 0
Minimum: 0
Maximum: 65535
Type: Read Only
13 [NAK Bad Packet]
(1)
Displays the number of NAKs sent by the serial
converter module because of corrupt packets
(improper protocol messages) as determined by the
module.
Default: 0
Minimum: 0
Maximum: 65535
Type: Read Only
(1)
This value is normally a low value. If it is continually incrementing and you are having
communications problems, use a lower baud rate or replace the 1203-SFC serial cable.
!
ATTENTION: Risk of injury or equipment damage exists. If the serial
converter module is transmitting I/O that controls the drive (indicated by a
solid green diamond LED), the drive may fault when you remove or reset the
module. Determine how your drive will respond before removing or resetting
a connected serial converter module.