Reference Manual Owner's manual
166 Rockwell Automation Publication 750-RM001F-EN-P - February 2012
Appendix B Parameter Data
Parameters and Settings in a
Linear List
This table lists the configurable parameters and their valid settings in numerical
order. If any values other than those listed in the table are configured for any of
the parameters, an Invalid Configuration fault occurs.
File
Group
No. Display Name
Full Name
Description
Values
Read-Write
Data Type
Safe Speed Monitor
Security
1Password
Password
Password for Lock and Unlock function.
Default:
Min/Max:
N/A
0 / 4294967295
RW 32-bit
Integer
5Lock State
Lock State
Command to lock or unlock the safety option configuration.
Default:
Options:
0 = “Unlock”
0 = “Unlock”
1 = “Lock”
RW 8-bit
Integer
6 Operating Mode
Operating Mode
Command to place the system in Program or Run mode.
Default:
Options:
0 = “Program”
0 = “Program”
1 = “Run”
2 = “Config Fault”
RW 8-bit
Integer
7 Reset Defaults
Reset Defaults
Resets safety option to factory defaults.
Default:
Options:
0 = “No Action”
0 = “No Action”
1 = “Reset Fac” (Reset to factory defaults)
RW 8-bit
Integer
10 Signature ID
Signature Identifier
Safety configuration identifier.
Default:
Min/Max:
N/A
0 / 4294967295
RO 32-bit
Integer
13 New Password
New Password
32-bit configuration password.
Default:
Min/Max:
N/A
0 / 4294967295
RW 32-bit
Integer
17 Password Command
Password Command
Save new password command.
Default:
Options:
0 = “No Action”
0 = “No Action”
1 = “Change PW” (Change Password)
2 = “Reset PW” (Reset Password)
RW 8-bit
Integer
18 Security Code
Security Code
Used for Reset Password command.
Default:
Min/Max:
N/A
0 / 65535
RO 32-bit
Integer
19 Vendor Password
Vendor Password
Vendor password for Reset Password command.
Default:
Min/Max:
N/A
0 / 65535
RW 16-bit
Integer