Reference Manual Owner's manual
Rockwell Automation Publication 750-RM001F-EN-P - February 2012 151
Chapter 12
Troubleshooting the PowerFlex Safety Option
Module
Introduction
This chapter provides troubleshooting tables for diagnosing fault conditions
associated with the PowerFlex safety option module.
Status Indicators
The safety option features two indicators to provide status information.
Topic Page
Status Indicators
151
Nonrecoverable Faults 152
Fault Recovery 152
Fault Codes and Descriptions 152
Fault Reactions 155
Status Attributes 156
Indicator Status Description
P/F Green/On The safety option is operating normally and is in Run mode.
Red/Flashing A recoverable fault has occurred.
Red/On A nonrecoverable fault has occurred.
(All other indicators are OFF.)
Red/Green Flashing The configuration is being downloaded or a firmware
upgrade is in progress.
MP Green/On Motion Power is enabled.
Off Motion Power is disabled.
Red/Flashing A Motion Power fault has been detected.