Port Assignment
When used in an Integrated Motion application, the Safe Torque Off
option must be installed in port 6.
Only one safety option module can be installed at a time. Multiple safety
options or duplicate safety option installations are not supported.
Jumper Settings
Ensure the hardware enable jumper (ENABLE) on the main control board
is installed. Refer to page 214
for location. If not installed, the drive will
fault when powered up.
Ensure the safety enable jumper (SAFETY) on the main control board is
removed (Frames 1…7 only). Refer to page 216
for location.