Manual

182 Rockwell Automation Publication 750-IN001N-EN-P - April 2014
PowerFlex 750-Series AC Drives
Table 21 - 690V, 60 Hz Input - Code P3 Thermal Magnetic Circuit Breaker Options
Table 22 - 690V, 60 Hz Input - Code P5 Molded Case Disconnect Switch Options (Floor Mount Frame
8 Only)
kW Amps Duty Line Side Terminal
Lugs
Terminal Size Recommended Torque
200 215 Heavy 140U-L-TL6A2 (2) 2…500 MCM kit of 3 42 N•m (375 lb•in)
250 265 Heavy 140U-L-TL6A2 (2) 2…500 MCM kit of 3 42 N•m (375 lb•in)
265 Normal 140U-L-TL6A2 (2) 2…500 MCM kit of 3 42 N•m (375 lb•in)
300 308 Heavy 140U-L-TL6A2 (2) 2…500 MCM kit of 3 42 N•m (375 lb•in)
315 330 Light 140U-L-TL6A2 (2) 2…500 MCM kit of 3 42 N•m (375 lb•in)
330 Normal 140U-L-TL6A2 (2) 2…500 MCM kit of 3 42 N•m (375 lb•in)
355 370 Heavy 140U-L-TL6A2 (2) 2…500 MCM kit of 3 42 N•m (375 lb•in)
370 Light 140U-L-TL6A2 (2) 2…500 MCM kit of 3 42 N•m (375 lb•in)
370 Normal 140U-L-TL6A2 (2) 2…500 MCM kit of 3 42 N•m (375 lb•in)
375 375 Heavy 140U-L-TL6A2 (2) 2…500 MCM kit of 3 42 N•m (375 lb•in)
400 410 Light 140U-L-TL6A2 (2) 2…500 MCM kit of 3 42 N•m (375 lb•in)
413 Heavy 140U-L-TL6A2 (2) 2…500 MCM kit of 3 42 N•m (375 lb•in)
415 Normal 140U-L-TL6A2 (2) 2…500 MCM kit of 3 42 N•m (375 lb•in)
450 460 Light 140U-L-TL6A2 (2) 2…500 MCM kit of 3 42 N•m (375 lb•in)
460 Normal 140U-L-TL6A2 (2) 2…500 MCM kit of 3 42 N•m (375 lb•in)
500 500 Light 140U-M-TLA2A (2) 500…750 MCM 56 N•m (500 lb•in)
500 Normal 140U-M-TLA2A (2) 500…750 MCM 56 N•m (500 lb•in)
530 530 Light 140U-M-TLA2A (2) 500…750 MCM 56 N•m (500 lb•in)
kW Amps Duty Line Side Terminal
Lugs
Terminal Size Recommended Torque
200 215 Heavy 140U-L-TL6A2 (2) 2…500 MCM kit of 3 42 N•m (375 lb•in)
250 265 Heavy 140U-L-TL6A2 (2) 2…500 MCM kit of 3 42 N•m (375 lb•in)
265 Normal 140U-L-TL6A2 (2) 2…500 MCM kit of 3 42 N•m (375 lb•in)
300 308 Heavy 140U-L-TL6A2 (2) 2…500 MCM kit of 3 42 N•m (375 lb•in)
315 330 Light 140U-L-TL6A2 (2) 2…500 MCM kit of 3 42 N•m (375 lb•in)
330 Light 140U-L-TL6A2 (2) 2…500 MCM kit of 3 42 N•m (375 lb•in)
355 370 Heavy 140U-L-TL6A2 (2) 2…500 MCM kit of 3 42 N•m (375 lb•in)
370 Light 140U-L-TL6A2 (2) 2…500 MCM kit of 3 42 N•m (375 lb•in)
370 Normal 140U-L-TL6A2 (2) 2…500 MCM kit of 3 42 N•m (375 lb•in)
375 375 Heavy 140U-L-TL6A2 (2) 2…500 MCM kit of 3 42 N•m (375 lb•in)
400 410 Light 140U-L-TL6A2 (2) 2…500 MCM kit of 3 42 N•m (375 lb•in)
413 Heavy 140U-L-TL6A2 (2) 2…500 MCM kit of 3 42 N•m (375 lb•in)
415 Normal 140U-L-TL6A2 (2) 2…500 MCM kit of 3 42 N•m (375 lb•in)
450 460 Light 140U-L-TL6A2 (2) 2…500 MCM kit of 3 42 N•m (375 lb•in)
460 Normal 140U-L-TL6A2 (2) 2…500 MCM kit of 3 42 N•m (375 lb•in)
500 500 Light 140U-M-TLA2A (2) 500…750 MCM 56 N•m (500 lb•in)
500 Normal 140U-M-TLA2A (2) 500…750 MCM 56 N•m (500 lb•in)
530 530 Light 140U-M-TLA2A (2) 500…750 MCM 56 N•m (500 lb•in)