Manual
Rockwell Automation Publication 750-IN001N-EN-P - April 2014 175
PowerFlex 750-Series AC Drives
21G…E825 LD 950 50 – – –
ND 900 50 – – –
HD 750 50 – – –
21G…E900 LD 1000 65 – – –
ND 950 50 – – –
HD 800 50 – – –
21G…E980 LD 1100 65 – – –
ND 1000 65 – – –
HD 900 50 – – –
(1) These circuit breakers are considered Branch Circuit Protection for the unit if the tap is within 10 ft. of the breaker input.
(2) These are 21G, SCCR ratings with no additional protection provided. Branch circuit protection (fuse) is required based on NEC guidelines for options with P5.
Drive Catalog
Number
Duty
Cycle Hp
Short Circuit Current Rating (kA)
Circuit Breaker
Only (P3)
(1)
Circuit Breaker with Input Contactor
(P3 with P11)
(1)
Molded Case Switch Only
(P5)
(2)
Molded Case Switch with Input Contactor
(P5 with P11)
(2)
600 Volt AC Input
Drive Catalog
Number
Duty
Cycle kW
Short Circuit Current Rating (kA)
Circuit Breaker
Only (P3)
Circuit Breaker with Input Contactor
(P3 with P11)
Molded Case Switch Only
(P5)
Molded Case Switch with Input Contactor
(P5 with P11)
690 Volt AC Input
21G…F265 LD 315 30 SCCR rating for 690V input contactor not
available at time of publication.
25 SCCR rating for 690V input contactor not
available at time of publication.
ND 250 30 25
HD 200 30 25
21G…F330 LD 355 30 25
ND 315 30 25
HD 250 30 25
21G…F370 LD 400 30 25
ND 355 30 25
HD 300 30 25
21G…F415 LD 450 30 25
ND 400 30 25
HD 355 30 25
21G…F460 LD 500 25 25
ND 450 30 25
HD 375 30 25
21G…F500 LD 530 25 25
ND 500 25 25
HD 400 30 25
21G…F590 LD 630 35 – – –
ND 560 35 – – –
HD 450 35 – – –
21G…F650 LD 710 35 – – –
ND 630 35 – – –
HD 500 35 – – –
21G…F710 LD 800 35 – – –
ND 710 35 – – –
HD 560 35 – – –
21G…F765 LD 850 35 – – –
ND 750 35 – – –
HD 630 35 – – –
21G…F795 LD 900 35 – – –
ND 800 35 – – –
HD 710 35 – – –
21G…F960 LD 1000 35 – – –
ND 900 35 – – –
HD 800 35 – – –