Manual

Rockwell Automation Publication 750-IN001N-EN-P - April 2014 111
PowerFlex 750-Series AC Drives
Common DC Input Drives
1. Disconnect the cabinet fan /cabinet blower assembly harnesses from
TB2-5 and TB2-6.
2. Disconnect the 120/240V control power input harness from TB2-3
and TB2-4.
3. Disconnect 120V UPS control power input (if used) from TB2-1 and
TB2-2.
4. Disconnect the digital I/O wiring (if used) from TB3
5. Disconnect the door interlock wiring (if used) from TB4
6. Disconnect the 120V UPS control power output wiring (if used) from
TB5.