Instruction Manual

Rockwell Automation Publication 2100-IN012E-EN-P - February 2012 67
Operator Handle and Unit Interlock Chapter 6
Lock Horizontal Operating Handles in the OFF/O Position
Some units use a horizontal operating handle. The horizontal operating handle
can be locked in the OFF/O position by putting the shackle of the lock through
the open slotted area to the left of the operator handle.
Figure 32 - Locking a Horizontally Mounted Operating Handle in OFF/O Position
Lock Units with Operating Handles in the ON/I Position
Follow this procedure to lock the operator handle in the ON/I position.
1. Drill out the hole to 3/8 in. (9.5 mm) diameter maximum.
2. Insert the shackle of the lock.
The following instructions assume that the handle is in the ON/I position:
For units with small handles, the hole is in the upper portion of the
operator handle assembly.
For units with medium and large operator handles, the hole is underneath
the operator handle on the handle assembly.
For units with a horizontally mounted handle, the hole is on the left-hand
side of the handle assembly.
ATTENTION: Locking an operating handle in the ON/I position may be in
conflict with local codes and emergency shut down requirements.