Rockwell Automation Publication 20Y-UM001E-EN-P - July 2014 99
Programming and Parameters Chapter 4
DYNAMIC CONTROL
Current Loop
064 [Active I Ref]
Displays the active current reference.
Default:
Min/Max:
Units:
Read Only
+/- 3200.0 Amp
0.1 Amp
065 [Reactive I Ref]
If selected by [Reactive I Sel], this parameter sets the reference for the reactive current. This can be
used for power factor correction of the power system. Positive value gives inductive current; negative
value gives capacitive current. The maximum reactive current is limited by the following formula:
Default:
Min/Max:
Units:
0.0 Amp
+/- Based on parameter 032 [Rated Amps]
0.1 Amp
066 [Active I Kp]
Sets the active current controller gain.
Default:
Min/Max:
Units:
400
0/4000
None
067 [Active I Ki]
Sets the integral gain of the active current controller.
Default:
Min/Max:
Units:
0.0266 sec
0.0000/6.0000 sec
0.0001 sec
068 [Reactive I Kp]
Sets the synchronization controller gain.
Default:
Min/Max:
Units:
2000
0/32000
None
069 [Reactive I Ki]
Sets the integral of the synchronization controller.
Default:
Min/Max:
Units:
0.040 sec
0.000/20.000 sec
0.001 sec
070 [Reactive I Sel]
Selects the source from which the reactive current is taken.
Default:
Options:
0
0
1
2
React I Ref
React I Ref
Analog In1
Analog In2
Limits
075 [Motor Power Lmt]
Sets the limit for motoring power on the AC line.
Default:
Min/Max:
Units:
300.0%
0.1/300.0%
0.1%
076 [Regen Power Lmt]
Sets the limit for regenerative power allowed to the AC line.
Default:
Min/Max:
Units:
-300.0%
-0.1/-300.0%
0.1%
077 [Current Lmt Val]
Sets the current limit value.
Default:
Min/Max:
Units:
1.5 x [Rated Amps]
0.0/Based on Unit Rating
0.1 Amps
078 [DC Bus Lo Alarm]
Sets the lowest acceptable DC bus voltage for the application. A warning is indicated if the DC bus
voltage falls below the value of this parameter.
Default:
Min/Max:
Units:
Based on Unit Rating
0.0/2000.0V DC
0.1V DC
079 [DC Bus Hi Alarm]
Sets the highest acceptable DC bus voltage for the application. A warning is indicated if the DC bus
voltage exceeds the value of this parameter.
Default:
Min/Max:
Units:
Based on Unit Rating
0.0/2000.0V DC
0.1V DC
080 [DC Ref Lo Lmt]
Displays the limit value of the DC bus reference low limitation, which is calculated based on the
voltage class x 1.35 x 1.05.
Default:
Min/Max:
Units:
Read Only
0.0/1500.0V DC
0.1V DC
081 [DC Ref Hi Lmt]
Displays the limit value of the DC bus reference high limitation, which is calculated based on the
voltage class x 1.35 x 1.3 (for 400/480V units) or voltage class x 1.35 x 1.15 (for 600/690V units).
Default:
Min/Max:
Units:
Read Only
0.0/1500.0V DC
0.1V DC
082 [Ground I Lvl]
Sets the limit value of ground current in % of the unit rating before a ground current alarm or fault is
activated. For AFE parallel operation, the values in all AFEs must be set to 100%.
Default:
Min/Max:
Units:
50.0%
0.0/100.0%
0.1% (Based on unit rating)
File
Group
No. Parameter Name & Description Values
Maximum Reactive I Ref = P032 [Rated Amps]
2
- P004 [Active Current]
2