Owner manual

42 Rockwell Automation Publication 20Y-UM001E-EN-P - July 2014
Chapter 1 AFE in IP20 2500 MCC Style Enclosure—Installation/Wiring
Table 5 - Recommended Control Wire for Digital I/O
Figure 20 - Door Control Box I/O Terminal Blocks and Jumpers
I/O Terminal Blocks
Table 6 - Door Control Box I/O Terminal Block Specifications for AFE in IP20 2500 MCC Style Enclosure
Type Wire Type(s) Description Minimum
Insulation Rating
Unshielded Per US NEC or applicable national or local code
300V, 60 °C
(140 °F)
Shielded Multi-conductor shielded cable such as Belden
8770(or equivalent)
0.5 mm
2
(22 AWG),
3 conductor, shielded
J1
J2
J3
J4
J5
Components mounted on inside
of AFE enclosure (see Figure 12
for location)
See Table 6
below for door control box item number descriptions and specifications.
Door Control Box Components
X3 Term. No. Default Description
57 and 60 Remote momentary pulse of 0.4…1.0 sec. across these terminals starts
precharge in REM mode when terminals 58 and 61 are remotely closed.
58 and 61 These terminals must be remotely closed to start precharge. Opening
these terminals opens the main contactor K1.
63 and 64 Remotely closing these terminals resets an AFE fault.
65 and 66 AFE run signal to the inverter enable input.
400 and 480 480
Control input voltage setting.
600 and 690 690
For jumper configurations,
see Table 8 on page 45
.
(X3 Terminals)
No. Name Description Wire Size Range
(1)
(1) Maximum/minimum that the terminal block will accept - these are not recommendations.
Torque
Maximum Minimum Maximum Recommended
Analog I/O Analog I/O Signals 2.5 mm
2
(14 AWG)
0.5 mm
2
(22 AWG)
0.2 N•m
1.8 lb•in
0.2 N•m
1.8 lb•in
Digital Inputs Digital Input Signals 2.5 mm
2
(14 AWG)
0.5 mm
2
(22 AWG)
0.2 N•m
1.8 lb•n
0.2 N•m
1.8 lb•in
Digital Outputs Digital Out Relays 2.5 mm
2
(14 AWG)
0.5 mm
2
(22 AWG)
0.5 N•m
4.5 lb•in
0.5 N•m
4.5 lb•in
Control Terminal Customer input and
output control
2.5 mm
2
(14 AWG)
0.5 mm
2
(22 AWG)
0.8 N•m
7.1 lb•in
0.8 N•m
7.1 lb•in