Chapter 4 Programming and Parameters
INPUTS & OUTPUTS
Analog Outputs
208 [Anlg Out Absolute]
Selects whether the signed value or absolute value of a parameter is used before being scaled to drive the analog
output.
209 [Analog Out1 Sel]
Selects the source for Analog Output 1.
Default:
Options:
0 = Input Volt
See Table
210 [Analog Out1 Hi]
Sets the Analog Output 1 value when the source value is at maximum.
Default:
Min/Max:
Units:
20.000 mA, 10.000V
4.000/20.000 mA
-/+10.000V
0.001 mA
0.001V
211 [Analog Out1 Lo]
Sets the Analog Output 1 value when the source value is at minimum.
Default:
Min/Max:
Units:
0.000 mA, 0.000V
4.000/20.000 mA
-/+10.000V
0.001 mA
0.001V
212 [Analog Out2 Sel]
Selects the source for Analog Output 2.
Default:
Options:
0 = AC Line Freq
See [Analog Out1 Sel]
Table
213 [Analog Out2 Hi]
Sets the Analog Output 2 value when the source value is at maximum.
Default:
Min/Max:
Units:
20.000 mA, 10.000V
4.000/20.000 mA
-/+10.000V
0.001 mA
0.001V
214 [Analog Out2 Lo]
Sets the Analog Output 2 value when the source value is at minimum.
Default:
Min/Max:
Units:
0.000 mA, 0.000V
4.000/20.000 mA
-/+10.000V
0.001 mA
0.001V
File
Group
No. Parameter Name & Description Values
Bit
Definition
Analog Out2
Analog Out1
Default xxxxxxxxxxxxxx11
Bit 1514131211109 8 7 6 5 4 3 2 1 0
1 = Absolute
0 = Signed
x = Reserved
Options [Analog Out1 Lo] Value [Analog Out1 Hi]
Value
Parameter [Anlg Out Absolut] =
Signed Absolute
0 Input Volt 0V AC 0V AC 200% Rated
(2)
(2) 100% corresponds to parameter 031 [Rated Volts].
1 AC Line Freq –63.0 Hz 0 Hz 63.0 Hz
2 Total Curr 0 Amps 0 Amps 200% Rated
(3)
(3) 100% corresponds to parameter 032 [Rated Amps].
3 Active Curr –200% Rated 0 Amps 200% Rated
(3)
4 ReactiveCurr –200% Rated 0 Amps 200% Rated
(3)
5 Input Curr R 0 Amps 0 Amps 200% Rated
(3)
6 Input Curr S 0 Amps 0 Amps 200% Rated
(3)
7 Input Curr T 0 Amps 0 Amps 200% Rated
(3)
8 DC Bus Volt 0V DC 0V DC 300% Rated
(2)
9 DC Bus Curr –200% Rated 0 Amps 200% Rated
(3)
10 AC Line kW –200% Rated 0 kW 200% Rated
(4)
(4) 100% corresponds to parameter 030 [Rated kW].
11 AC Line kVar –200% Rated 0 kVar 200% Rated
(4)
12 AC Line kVA 0 kVA 0 kVA 200% Rated
(4)
13 Power Factor -1.00 0 1.00
14 DC Bus V Ref P080 [V DC] P080 [V DC] P081 [V DC]
15 Param Cntl
(1)
(1) Parameter controlled analog output allows PLC to control analog outputs through datalinks.
Set in parameter 217 [Anlg Out1 Setpt] and parameter 218 [Anlg Out2 Setpt].
———
16 TestPt Data1 -32767 0 32767