Owner manual
104 Rockwell Automation Publication 20Y-UM001E-EN-P - July 2014
Chapter 4 Programming and Parameters
UTILITY
Diagnostic
108 [Status 1 @ Fault]
Captures and displays the bit pattern of parameter 095 [Cnvrtr Status 1] at the time of the last fault.
Read Only
109 [Status 2 @ Fault]
Captures and displays the bit pattern of parameter 096 [Cnvrtr Status 2] at the time of the last fault.
Read Only
110 [Alarm 1 @ Fault]
Captures and displays the bit pattern of parameter 097 [Cnvrtr Alarm 1] at the time of the last fault.
Read Only
111 [Alarm 2 @ Fault]
Captures and displays the bit pattern of parameter 098 [Cnvrtr Alarm 2] at the time of the last fault.
Read Only
112 [Testpoint 1 Sel]
Selects the function whose value is displayed in parameter 113 [Testpoint 1 Data]. These are internal values
that are not accessible through parameters.
Default:
Min/Max:
Units:
499
0/65535
None
113 [Testpoint 1 Data]
Displays the present value of the function selected in parameter 112 [Testpoint 1 Sel].
Default:
Min/Max:
Units:
Read Only
-/+32767
None
114 [Testpoint 2 Sel]
Selects the function whose value is displayed in parameter 115 [Testpoint 2 Data]. These are internal values
that are not accessible through parameters.
Default:
Min/Max:
Units:
499
0/65535
None
115 [Testpoint 2 Data]
Displays the present value of the function selected in parameter 114 [Testpoint 2 Sel].
Default:
Min/Max:
Units:
Read Only
-/+32767
None
116 [Cnvrtr OL Count]
Displays the accumulated percentage of AFE overload. Continuously operating the AFE over the set level will
increase this value to 100% and cause an AFE fault.
Default:
Min/Max:
Units:
Read Only
0.1%/+100.0%
0.1%
File
Group
No. Parameter Name & Description Values
Bit
Definition
DCVoltRefD2
DCVoltRefD1
DCVoltRefD0
Cmd Delayed
Regen CurLim
Mot CurLim
At Reference
Faulted
Alarm
Droop Active
In Precharge
Regenerating
Motoring
Active
Ready
Default x000000000000000
Bit 1514131211109 8 7 6 5 4 3 2 1 0
1 = Condition True
0 = Condition False
x = Reserved
Bits Description
14 13 12
0
0
0
0
1
1
1
1
0
0
1
1
0
0
1
1
0
1
0
1
0
1
0
1
DC Volt Ref
Analog In1
Analog In2
DPI Port 1
DPI Port 2
DPI Port 3
DPI Port 4
DPI Port 5
Bit
Definition
DPI at 500 k
AutoRst Act
AutoRst Ctdn
ModIndexLim
Active
Ready
Default xx0xxx00xxxxx000
Bit 1514131211109 8 7 6 5 4 3 2 1 0
1 = Condition True
0 = Condition False
x = Reserved
Bit
Definition
Overload
DCBusHiAlarm
DCBusLoAlarm
DCRefHighLim
DCRefLowLim
LCL Fan Stop
HeatsinkOvTp
LineSyncFail
Anlg In Loss
DC UnderVolt
Prechrg Actv
Default x0x0000000000000
Bit 1514131211109876543210
1 = Condition True
0 = Condition False
x = Reserved
Bit
Definition
Contact Fdbk
DigInConflct
Default xxxxxxxxxxx0xx00
Bit 1514131211109876543210
1 = Condition True
0 = Condition False
x = Reserved