Owner manual

Rockwell Automation Publication PFLEX-IN029B-EN-P - August 2014 35
PowerFlex 700H and 700S Drives - Frame 9 Procedures Chapter 1
9. Install the new fan inverter assembly in the reverse order of removal.
IMPORTANT
If you are servicing a 400V/480V Frame 9 drive, insert the jumper on connector
X3 as shown here.
Connect Jumper to Connector X3
X8
X2
IMPORTANT
Verify that dip switch S1 on the new fan iverter board is properly configured, as
shown below.
X6
X1
X4
X5
X7
S1
X2 X8
1
ON
2
3 4
S1
1
ON
2
34
S1-1 S1-2 S1-3 S1-4
Off Off On Off
Switch Setting To Indicate the Following:
S1 Off 50 Hz Fan Motor Frequency
S2 Off 220 V AC Motor Voltage
S3 On 230 V AC Motor Voltage
S4 Off Frame Size 9…14