Owner manual

134 Rockwell Automation Publication PFLEX-IN029B-EN-P - August 2014
Chapter 5 PowerFlex 700H and 700S Drives - Frame 13 Procedures
Frame 13 Fan System
Replacement Procedures
Replacement procedures for these frame 13 fan system parts are included in this
chapter.
Remove Power from the Drive
1. Turn off and lock out input power.
2. Wa i t f i ve m i n ut e s .
3. Check the DC bus voltage at the Power Terminal Block by measuring
between the +DC and -DC terminals, between the +DC terminal and the
chassis, and between the -DC terminal and the chassis. The voltage must
be zero for all three measurements.
Cat. No. Part Description Page
20-PP01096 60 mm cooling fan for the ASIC board assembly 139
20-PP20202 Fuse for fan system 141
20-PP20300 Fuse holder for the fan system fuses 141
20-FR13301 AC fan inverter 145
20-VB00299 Main AC fan inverter circuit board 151
SK-H1-DCFANBD1 Main DC fan power supply circuit board 153
SK-Y1-DCFANRETROFIT-F13 Fan system retrofit kit 154
SK-H1-FANCAP-F1314 Main AC fan capacitor (7 μF) kit 170
20-FI3300 230 W main AC fan assembly 174
SK-Y1-DCFAN1 Main DC fan assembly 174
ATTENTION: To avoid an electric shock hazard, verify that the voltage on the bus
capacitors has discharged completely before servicing. Check the DC bus voltage
at the Power Terminal Block by measuring between the +DC and -DC terminals,
between the +DC terminal and the chassis, and between the -DC terminal and
the chassis. The voltage must be zero for all three measurements.
Remove power before making or breaking cable connections. When you remove or
insert a cable connector with power applied, an electrical arc may occur. An
electrical arc can cause personal injury or property damage by:
sending an erroneous signal to your systems field devices, causing unintended
machine motion
causing an explosion in a hazardous environment
Electrical arcing causes excessive wear to contacts on both the module and its
mating connector. Worn contacts may create electrical resistance.