Appendix C Application Notes
Curve B - If the field current curve fine tuning procedure is completed, the
flux current to flux reference curve will follow a curve determined by the
real flux percentage of Par 500 [Flux Ref Pct] necessary to determine the
circulation of the field current for the connected system. See the Current
Regulator block diagram on page 326
.
Field Current Curve Tuning Procedure:
1. Reset the field current curve by setting Par 920 [Reset Fld Curve] to “1”.
2. Configure the following parameters:
Enter the percentage (100%) of the maximum motor nameplate rated
armature voltage in Par 921 [Out Volt Level]
Set Par 469 [Field Mode Sel] = 0 “Base Speed”
Set Par 467 [Max Fld Curr Pct] = 100%
3. Start the drive.
4. Increase the motor speed until the value (electromotive force) displayed in
Par 233 [Output Voltage] corresponds to the value previously set in Par 175
[Rated Motor Volt].
5. Decrease the value of Par 467 [Max Fld Curr Pct] until the value displayed in
Par 233 [Output Voltage] is equal to 90% of Par 175 [Rated Motor Volt].
When you have reached this value, read the value displayed in Par 234 [Fld
Current Pct] and enter the value into Par 918 [Fld Const 90 Pct].
6. Decrease the value of Par 467 [Max Fld Curr Pct] until the value displayed in
Par 233 [Output Voltage] is equal to 70% of Par 175 [Rated Motor Volt].
When you have reached this value, read the value displayed in Par 234 [Fld
Current Pct] and enter the value into Par 917 [Fld Const 70 Pct].
7. Decrease the value of Par 467 [Max Fld Curr Pct] until the value displayed in
Par 233 [Output Voltage] is equal to 40% of Par 175 [Rated Motor Volt].
When you have reached this value, read the value displayed in Par 234 [Fld
Current Pct] and enter the value into Par 916 [Fld Const 40 Pct].
8. Stop the drive.
9. Set the desired method of field control in Par 469 [Field Mode Sel] (0 “Base
Speed” or 1 “Field Weaken”)
10. Reset the value of 467 [Max Fld Curr Pct] to 100%.
If you change the value of Par 175 [Rated Motor Volt] or par 280 [Nom Mtr Fld
Amps], the field current curve will need to be re-tuned.