Owner's manual
230 Rockwell Automation Publication 20P-UM001I-EN-P - February 2013
Appendix A Supplemental Drive Information
Figure 69 - Frame D Regenerative Drive - Leg Fuse Location
Fuses for Non-Regenerative Frame C and D Drives
AC input line and/or leg fuses are internally mounted and provided with frames
C and D drives. See Fuse Code FS4 in Figure 65
on page 225. Also, see Figure 70
on page 232
for fuse locations.
Table 67 - Recommended AC Input Line Fuses - 230V AC Input Frame C Drives
Table 68 - Recommended Leg Fuses - 230V AC Input Frame D Drives
Table 69 - Recommended AC Input Line Fuses - 460V AC Input Frame C Drives
Leg fuses and switches are located on the bus bars behind the control panel, which holds the circuit boards.
Frame
Drive
Current
Rating
Code
DC
Amps
AC Line
Amps
Qty Bussmann Ferraz Shawmut (Gould Shawmut) SIBA
Square Body - Flush End Contact
C 521 521 426 3 170M5466 + switch 170H0069 6,9 URD 32 TTF 1000 + switch MS 3-V1-5 BS 20 671 32.1000 + switch 28 001 04
700 700 571 3 170M5466 + switch 170H0069 6,9 URD 32 TTF 1000 + switch MS 3V 1-5 BS 20 671 32.1000 + switch 28 001 04
Frame
Drive
Current
Rating
Code
DC
Amps
AC Line
Amps
Qty Bussmann Ferraz Shawmut (Gould Shawmut) SIBA
Square Body - DIN 43653 Stud-Mount
D 875 875 715 6 170M6263 + switch 170H0069 Y300263 + switch MS 3V 1-5 UR 20 635 32.900 + switch 28 001 04
1K0 1050 858 6 170M6264 + switch 170H0069 Z300264 + switch MS 3V 1-5 UR 20 635 32.1000 + switch 28 001 04
Frame
Drive
Current
Rating
Code
DC
Amps
AC Line
Amps
Qty Bussmann Ferraz Shawmut (Gould Shawmut) SIBA
Square Body - Flush End Contact
C 495 495 404.4 3 170M5464 + switch 170H0069 6,9 URD 32 TTF 800 + switch MS 3-V1-5 BS 20 671 32.800 + switch 28 001 04
667 667 544.9 3 170M5466 + switch 170H0069 6,9 URD 32 TTF 1000 + switch MS 3-V1-5 BS 20 671 32.1000 + switch 28 001 04