Owner's manual
Rockwell Automation Publication 20P-UM001I-EN-P - February 2013 225
Supplemental Drive Information Appendix A
Frame C and D Fuse Information
All fuses for armature and field circuit protection are internally mounted and
provided with frame C and D drives.
Figure 65 - Frame C and D Fuse Table Designations
Frame C and D Recommended Field Circuit Fuses
Field circuit fuses for frames C and D drives are internally mounted (labeled FU1
and FV1) and provided with the drive. See Fuse Code FS3 in Figure 65
above.
Also, see Figure 66
on page 226 and Figure 67 on page 227 for locations.
Table 55 - 230V AC Input Drives
Table 56 - 460V AC Input Drives
Frame
Drive
Current
Rating
Code
Field
Amps
Type Qty Bussmann Ferraz Shawmut (Gould
Shawmut)
SIBA
C 521 20 10 x 38 mm
2
FWC-25A10F A60Q25-2 6003305.25
D875
40 22 x 58 mm FWP-50A22F A70QS50-22F 5014006.50
1K0
Frame
Drive
Current
Rating
Code
Field
Amps
Type Qty Bussmann Ferraz Shawmut
(Gould Shawmut)
SIBA
C 495
20 10 x 38 mm
2
FWC-25A10F
A60Q25-2
6003305.25
667 A60Q25-8
D 830
40
22 x 58 mm
FWP-50A22F A70QS50-22F 5014006.50
996
1K1
70 FWP-100A22F A70QS100-22F 5014006.1001K3
1K4
U V W
C D
FS3
FS4
C1 D1
U1 V1
M
FS3 = Internally
mounted fuses for
the field circuit on
the AC input side.
FS4 = Internally
mounted fuses for
the armature
converter on the AC
input side.