Owner's manual

Rockwell Automation Publication 20P-UM001I-EN-P - February 2013 221
Supplemental Drive Information Appendix A
Table 48 - 575V AC Input Drives
Frame A and B Recommended Armature DC Output Fuses
Armature DC output fuses are externally mounted for frame A and B drives and
must be sourced separately. These fuses are required on four quadrant drives only,
but highly recommended on two quadrant drives. See Fuse Code FS2 in
Figure 62
on page 219.
Table 49 - 230V AC Input Drives
Frame Drive
Current
Rating Code
DC Amps AC Line
Amps
Bussmann Ferraz Shawmut
(Gould Shawmut)
North American
FWP Type
North American FWP
Fuse Block
North American A70QS Type
B 067 67.5 55.1 FWP-100A A70QS100-4
101 101.3 82.7 FWP-175A BH-1133 A70QS175-4K
135 135 110.3 FWP-225A A70QS225-4
270 270 220.6 FWP-450A BH-3144 A70QS450-4
405 405 330.9 FWP-600A A70QS600-4K
Frame
Drive
Current
Rating
Code
DC
Amps
AC Line
Amps
Bussmann Ferraz Shawmut (Gould Shawmut)
Ferrule FWP
Type
Ferrule Fuse
Block
North American
FWP Type
North
American
Fuse Block
Ferrule A70QS
Type
North American A70P
/ A70QS Type
A 7P0 7 5.7 FWP-15A14F
CH142D
FWP-15B A70QS16-14F A70P15-4
9P0 9 7.4 FWP-20A14F FWP-20B A70QS20-14F A70P20-4
012 12 9.8 FWP-25A14F FWP-25B A70QS25-14F A70P25-4
020 20 16 FWP-40A14F FWP-40B A70QS40-14F A70QS40-4
029 29 24 FWP-63A22F
CH222D
FWP-60B A70QS63-22F A70QS60-4
038 38 31 FWP-80A22F FWP-80B A70QS80-22F A70QS80-4
055 55 45 FWP-125A
BH-1133
A70QS125-4K
073 73 60 FWP-150A A70QS150-4K
093 93 76 FWP-200A A70QS200-4K
110 110 90 FWP-225A A70QS250-4
B 146 146 119 FWP-300A A70QS300-4
180 180 147 FWP-350A A70QS350-4
218 218 178 FWP-450A
BH-3144
A70QS450-4
265 265 217 FWP-600A A70QS600-4K
360 360 294 FWP-700A A70QS700-4
434 434 355 FWP-900A A70P900-4