Owner's manual
Rockwell Automation Publication 20P-UM001I-EN-P - February 2013 185
Programming and Parameters Chapter 3
INPUT / OUTPUT
Digital Inputs
564 [Dig In Status]
Status of the digital inputs.
Read Only
565
566
567
568
569
570
571
572
573
574
575
576
[Dig In Term 1]
[Dig In Term 2]
[Dig In Term 3]
[Dig In Term 4]
[Dig In Term 5]
[Dig In Term 6]
[Dig In Term 7]
[Dig In Term 8]
[Dig In Term 9]
[Dig In Term 10]
[Dig In Term 11]
[Dig In Term 12]
Status of the digital inputs.
0 = Low
1 = High
Default:
Min/Max:
Read Only
0 / 1
16-bit
Int
1276
1277
1278
1279
1280
1281
1282
1283
1387
1388
1389
1390
[Inversion In 1]
[Inversion In 2]
[Inversion In 3]
[Inversion In 4]
[Inversion In 5]
[Inversion In 6]
[Inversion In 7]
[Inversion In 8]
[Inversion In 9]
[Inversion In 10]
[Inversion In 11]
[Inversion In 12]
inverts the digital input signal.
Default:
Options:
0
0 =
1 =
“Disabled”
“Disabled”
“Enabled”
16-bit
Int
1391 [ContactorControl]
Selects the type of contactor to be controlled by the drive. Either style of
contactor (AC or DC) can be used, with or without dynamic braking (DB)
contactor.
• “AC Cntctr” indicates an AC contactor is used. See note 1 below.
• “AC Cntctr+DB” indicates that an AC contactor and dynamic brake
resistor is used. See note 1 below.
• “DC Cntctr” indicates a DC contactor is used.
• “DC Cntctr+DB” indicates that a DC contactor and dynamic brake resistor
is used.
The type of control selected determines how many I/O points will be
required for contactor control and status.
• “AC Cntctr” or “DC Cntctr” = 1 (relay) digital output, 1 digital input is
used.
• “AC Cntctr+DB” or “DC Cntctr+DB” = 2 (relay) digital outputs, 1 digital
input is used.
Notes:
• 1. When 1 “AC Cntctr” or 2 “AC Cntctr+DB” is selected, there is a 400 ms
delay to power up before SCR firing can begin. The delay is needed to
determine correct input voltage phasing.
• 2. Option 1 was changed from “Contactor”, option 2 was changed from
“Contactor+DB”, and options 3 and 4 were added for firmware version
2.001.
Default:
Options:
1 =
0 =
1 =
2 =
3 =
4 =
“AC Cntctr”
“None”
“AC Cntctr”
“AC Cntctr+DB”
“DC Cntctr”
“DC Cntctr+DB”
16-bit
Int
File
Group
No.
Parameter Name & Description
See page 110 for symbol descriptions
Values
Data Type
Related
Options
Reserved
Reserved
Reserved
Reserved
Digital In12
Digital In11
Digital In10
Digital In9
Digital In8
Digital In7
Digital In6
Digital In5
Digital In4
Digital In3
Digital In2
Digital In1
Default xxxx000000000000
Bit 1514131211109876543210
A
A