Instruction Manual

Publication 20P-IN061A-EN-P
PowerFlex® DC Drive
Frame D Bimetal Thermostat
Installation Instructions
What This Kit Includes
Bimetal thermostat and cable with connector
Thermal grease
Tools That You Need
Flathead screwdriver
Hexalobular screwdriver
Torque wrench
What You Need to Do
The bimetal thermostat is located on the heatsink of the U phase SCR leg
assembly in the drive. To install the bimetal thermostat:
Step 1: Remove power from the drive
Step 2: Remove the protective cover and open the control panel
Step 3: Remove the existing bimetal thermostat
Step 4: Install the new bimetal thermostat
Step 5: Install the protective cover, close the control panel and document
the change
ATTENTION: Only qualified personnel familiar with DC drives
and associated machinery should plan or implement the installation,
start-up and subsequent maintenance of the system. Failure to comply
may result in personal injury and/or equipment damage.
ATTENTION: To avoid an electric shock hazard, ensure that all
power to the drive has been removed before performing the following.