6 PowerFlex® DC Drive - Frame C Field Snubber Circuit Board
3. Disconnect the cable from connector XSW on the Switching Power
Supply board and lower the Control EMI shield until it rests on the
drive chassis.
Important: If the drive is not in a vertical position, the Control EMI
shield will not stay open without a means of restraint.
Figure 1 Field Snubber Board Layout
Remove cable
TA1
X3
1
XFCD
1
2U1
2V1
2C1 2C1
2D1 2D1