Owner's manual

16 Rockwell Automation Publication 20P-IN009D-EN-P - February 2012
PowerFlex DC Drive Frame B Pulse Transformer Circuit Board
Pulse Transformer Board FIR2-XX Rev. “N” and Higher
Set DIP switches S3 and S4, located at the bottom right corner of the Pulse
Transformer board (see Figure 1 - on page 5
for location), to the correct settings
based on the appropriate table below.
Table 5 - 230V AC Input Drives
Table 6 - 460V AC Input Drives
XSW1
XI2CA
X3
XP
TR2 TR1
XR
X4
XY
XCD_IO
TO5
TO3
TO6
TO1
TO4
TO2
KGO1
KGO4
KGO2
KGO5
KGO3
KGO6
T5
T3
T6
T1
T2
KG1
KG4
KG2
KG5
KG3
KG6
XCT
C
U
PE
PE1
V
XTA
XM
D
78 79 35 36 75 76 U2 V2
W
S3 S4
1U2
1V2
T4
1
D
79 35 36 75 76 U2 V2
S3 S4
1
Dip switches S3 and S4 are located at
the bottom, right corner of the board.
IMPORTANT
A blank cell below a switch in the following tables indicate that the setting is
“OFF”.
Drive
Current
Rating
Code
DC
Amps
AC Line
Amps
HP DIP Switch S3 DIP Switch S4
S3-1 S3-2 S3-3 S3-4 S3-5 S3-6 S3-7 S3-8 S4-1 S4-2 S4-3 S4-4 S4-5 S4-6 S4-7 S4-8
146 146 119 40 ON ON ON
180 180 147 50 ON ON ON ON
218 218 178 60 ON ON ON ON
265 265 217 75 ON ON ON ON
360 360 294 100 ON ON ON
434 434 355 125 ON ON ON ON
Drive
Current
Rating
Code
DC
Amps
AC Line
Amps
HP DIP Switch S3 DIP Switch S4
S3-1 S3-2 S3-3 S3-4 S3-5 S3-6 S3-7 S3-8 S4-1 S4-2 S4-3 S4-4 S4-5 S4-6 S4-7 S4-8
167 167 136.4 100 ON ON ON ON
207 207 169.1 125 ON ON ON
250 250 204.3 150 ON ON ON ON
330 330 269.6 200 ON ON ON
412 412 336.6 250 ON ON ON ON