Instruction Manual

4-2 Troubleshooting
Drive Status
The condition or state of your drive is constantly monitored. Any changes
will be indicated by the INV. STATUS LED on the DPI Communication
Interface Board and/or the HIM (if present).
Front Panel LED Indications
Figure 4.1 Typical Inv. Status LED Indications
HIM Indication
The LCD HIM also provides visual notification of a fault or alarm condition.
DPI Port 3
I NV. S TAT U S
Rockwell Automation
Color State Description
Green Flashing Drive ready, but not running & no faults are present.
Steady Drive running, no faults are present.
Yellow Flashing A Type 2 (non-configurable) alarm condition exists, drive continues to run.
Steady A Type 1 (user configurable) alarm condition exists, but drive continues to run.
Red Flashing A fault has occurred. Check [Fault x Code] or Fault Queue.
Steady A non-resettable fault has occurred.
Condition Display
Drive is indicating a fault.
The LCD HIM immediately reports the fault condition by displaying the
following:
“Faulted” appears in the status line
Fault number
Fault name
Time that has passed since fault occurred
Press Esc to regain HIM control.
Drive is indicating an alarm.
The LCD HIM immediately reports the alarm condition by displaying
the following:
Alarm name (Type 2 alarms only)
Alarm bell graphic
F-> Faulted Auto
0.0
Hz
Main Menu:
Diagnostics
Parameter
— Fault — F 5
OverVoltage
Time Since Fault
0000:23:52
F-> Power Loss Auto
0.0
Hz
Main Menu:
Diagnostics
Parameter
Device Select