Inputs & Outputs File
File
Group
No.
Parameter Name & Description
See page 3-2 for symbol descriptions
Values Related
INPUTS & OUTPUTS
Analog Inputs
320 [Anlg In Config]
Selects the mode for the analog inputs.
322, 323
321 [Anlg In Sqr Root]
Enables/disables the square root function for each input.
322
325
[Analog In 1 Hi]
[Analog In 2 Hi]
Sets the highest input value to the analog input x scaling block.
[Anlg In Config]
, parameter 320 defines if this input will be –/+10V or 4-20
mA.
Default:
Min/Max:
Units:
10.000 Volt
10.000 Volt
4.000/20.000mA
–/+10.000V
0.000/10.000V
0.001 mA
0.001 Volt
091
, 092
323
326
[Analog In 1 Lo]
[Analog In 2 Lo]
Sets the lowest input value to the analog input x scaling block.
[Anlg In Config]
, parameter 320 defines if this input will be –/+10V or 4-20
mA.
Default:
Min/Max:
Units:
0.000 Volt
0.000 Volt
4.000/20.000mA
–/+10.000V
0.000/10.000V
0.001 mA
0.001 Volt
091
, 092
324
327
[Analog In 1 Loss]
[Analog In 2 Loss]
Selects drive action when an analog signal loss is detected. Signal loss is
defined as an analog signal less than 1V or 2mA. The signal loss event
ends and normal operation resumes when the input signal level is greater
than or equal to 1.5V or 3mA.
Default:
Options:
0
0
0
1
2
3
4
5
6
“Disabled”
“Disabled”
“Disabled”
“Fault”
“Hold Input”
“Set Input Lo”
“Set Input Hi”
“Goto Preset1”
“Hold OutFreq”
091
, 092
340 [Anlg Out Config]
Selects the mode for the analog outputs.
0xx 0xxxxxxxxxxxx
10 01234567891112131415
1 =Current
0 =Voltage
x =Reserved
Bit #
Factory Default Bit Values
Analog In 1
Analog In 2
0xx 0xxxxxxxxxxxx
10 01234567891112131415
1 =Enable
0 =Disable
x =Reserved
Bit #
Factory Default Bit Values
Analog In 1
Analog In 2
xxx 1xxxxxxxxxxxx
10 01234567891112131415
1 =Current
0 =Voltage
x =Reserved
Bit #
Factory Default Bit Values
Analog Out1