Instruction Manual
3-22 Programming and Parameters
UTILITY
Diagnostics
216 [Dig In Status]
Status of the digital inputs.
Read Only 361 thru 366
217 [Dig Out Status]
Status of the digital outputs.
Read Only 380 thru 384
218 [Drive Temp]
Present operating temperature of the drive power section.
Default:
Min/Max:
Units:
Read Only
0.0/100.0%
0.1%
219 [Drive OL Count]
Accumulated percentage of drive overload. Continuously operating the
drive over 100% of its rating will increase this value to 100% and cause a
drive fault or foldback depending on the setting of [Drive OL Mode].
Default:
Min/Max:
Units:
Read Only
0.0/100.0%
0.1%
150
220 [Motor OL Count]
Accumulated percentage of motor overload. Continuously operating the
motor over 100% of the motor overload setting will increase this value to
100% and cause a drive fault.
Default:
Min/Max:
Units:
Read Only
0.0/100.0%
0.1%
047, 048
224 [Fault Frequency]
Captures and displays the output speed of the drive at the time of the last
fault.
Default:
Min/Max:
Units:
Read Only
0.0/+[Maximum Freq]
0.1 Hz
225 thru 230
225 [Fault Amps]
Captures and displays motor amps at the time of the last fault.
Default:
Min/Max:
Units:
Read Only
0.0/[Rated Amps] × 2
0.1 Amps
224 thru 230
226 [Fault Bus Volts]
Captures and displays the DC bus voltage of the drive at the time of the
last fault.
Default:
Min/Max:
Units:
Read Only
0.0/Max Bus Volts
0.1 VDC
224 thru 230
227 [Status 1 @ Fault]
Captures and displays [Drive Status 1] bit pattern at the time of the last fault.
Read Only 209,
224
thru 230
228 [Status 2 @ Fault]
Captures and displays [Drive Status 2] bit pattern at the time of the last fault.
Read Only 210,
224
thru 230
File
Group
No.
Parameter Name & Description
See page 3-2 for symbol descriptions
Values Related
000000xxxxxxxxxx
10 01234567891112131415
1 =Input Present
0 =Input Not Present
x =Reserved
Bit #
Digital In1
Digital In2
Digital In3
Digital In4
Digital In5
Digital In6
0xx 0xxxxxxxxxxxx
10 01234567891112131415
1 =Output Energized
0 =Output De-energized
x =Reserved
Bit #
Digital Out1
Digital Out2
0110000101110000
10 01234567891112131415
1 =Condition True
0 =Condition False
x =Reserved
Bit #
Ready
Active
Command Dir
Actual Dir
Accelerating
Decelerating
Alarm
Faulted
At Speed
Local ID 0
Local ID 1
Local ID 2
Spd Ref ID 0
Spd Ref ID 1
Spd Ref ID 2
Spd Ref ID 3
0000000x000000xx
10 01234567891112131415
1 =Condition True
0 =Condition False
x =Reserved
Bit #
Ready
Active
Running
Jogging
Stopping
DC Braking
AutoTuning
AutoRst Ctdn
AutoRst Act
Curr Limit
Bus Freq Reg
Motor Overld
DPI at 500 k