Instruction Manual
Programming and Parameters 3-21
UTILITY
Diagnostics
211 [Drive Alarm 1]
Alarm conditions that currently exist in the drive.
Read Only 212
212 [Drive Alarm 2]
Alarm conditions that currently exist in the drive.
Read Only 211
213 [Speed Ref Source]
Displays the source of the speed reference to the drive.
Default:
Options: 0
1
2
3-8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
Read Only
“PI Output”
“Analog In 1”
“Analog In 2”
“Reserved”
“MOP Level”
“Jog Speed”
“Preset Spd1”
“Preset Spd2”
“Preset Spd3”
“Preset Spd4”
“Preset Spd5”
“Preset Spd6”
“Preset Spd7”
“DPI Port 1”
“DPI Port 2”
“DPI Port 3”
“DPI Port 4”
“DPI Port 5”
“Reserved”
090
, 093,
096
, 101
214 [Start Inhibits]
Displays the inputs currently preventing the drive from starting.
Read Only
215 [Last Stop Source]
Displays the source that initiated the most recent stop sequence. It will be
cleared (set to 0) during the next start sequence.
Default:
Options: 0
1-5
6
7
8
9
10
11
Read Only
“Pwr Removed”
“DPI Port 1-5”
“Reserved”
“Digital In”
“Fault”
“Not Enabled”
“Sleep”
“Jog”
361
, 362,
363
, 364,
365
, 366
File
Group
No.
Parameter Name & Description
See page 3-2 for symbol descriptions
Values Related
000000x0000xxxxx
10 01234567891112131415
1 =Condition True
0 =Condition False
x =Reserved
Bit #
Prechrg Actv
UnderVoltage
Power Loss
Str At PwrUp
Anlg in Loss
IntDBRes OH
Drv OL Lvl 1
Drv OL Lvl 2
Decel Inhibt
Waking
0000000000000xxx
10 01234567891112131415
1 =Condition True
0 =Condition False
x =Reserved
Bit #
DigIn CflctA
DigIn CflctB
DigIn CflctC
Bipolr Cflct
MtrTyp Cflct
NP Hz Cflct
MaxFrq Cflct
VHz NegSlope
IR Vlts Rang
FlxAmps Rang
SpdRef Cflct
Ixo Vlt Rang
Sleep Config
0000100x100000xx
10 01234567891112131415
1 =Inhibit True
0 =Inhibit False
x =Reserved
Bit #
Fault
Type 2 Alarm
Enable
DC Bus Pchrg
Stop Assertd
Params Reset
Startup Actv
Digital In
DPI Port 1
DPI Port 2
DPI Port 3
DPI Port 4
DPI Port 5