Instruction Manual
Programming and Parameters 3-19
Utility File
File
Group
No.
Parameter Name & Description
See page 3-2 for symbol descriptions
Values Related
UTILITY
Direction Config
190 [Direction Mode]
Selects the method for changing drive direction.
Default:
Options:
0
0
1
2
“Unipolar”
“Unipolar”
“Bipolar”
“Reverse Dis”
320 thru 327
361 thru 366
HIM Ref Config
192 [Save HIM Ref]
Enables a feature to save the present frequency reference value issued by the HIM to Drive memory on power loss.
Value is restored to the HIM on power up.
193 [Man Ref Preload]
Enables/disables a feature to automatically load the present “Auto”
frequency reference value into the HIM when “Manual” is selected. Allows
smooth speed transition from “Auto” to “Manual.”
Default:
Options:
0
0
1
“Disabled”
“Disabled”
“Enabled”
MOP Config
194 [Save MOP Ref]
Enables/disables the feature that saves the present MOP frequency reference at power down or at stop.
195 [MOP Rate]
Sets rate of change of the MOP reference in response to a digital input.
Default:
Min/Max:
Units:
1.0 Hz/s
0.2/[Maximum Freq]
0.1 Hz/s
Drive Memory
196 [Param Access Lvl]
Selects the parameter display level.
Basic = Reduced parameter set
Advanced = Full parameter set
Default:
Options:
0
0
1
2
“Basic”
“Basic”
“Advanced”
“Reserved”
197 [Reset To Defaults]
Resets parameters to factory defaults except [Language], [Param Access
Lvl], and [Voltage Class] (params. 196, 201, and 202).
• Option 1 resets parameters to factory defaults based on [Voltage
Class].
• Options 2 and 3 will reset parameters to factory defaults and set
[Voltage Class] to low or high voltage settings.
Default:
Options:
0
0
1
2
3
“Ready”
“Ready”
“Factory”
“Low Voltage”
“High Voltage”
041 thru 047
054, 063,
069
thru 072
082, 148,
158
198 [Load Frm Usr Set]
Loads a previously saved set of parameter values from a selected user
set location in drive nonvolatile memory to active drive memory.
Default:
Options:
0
0
1
2
3
“Ready”
“Ready”
“User Set 1”
“User Set 2”
“User Set 3”
199
199 [Save To User Set]
Saves the parameter values in active drive memory to a user set in drive
nonvolatile memory.
Default:
Options:
0
0
1
2
3
“Ready”
“Ready”
“User Set 1”
“User Set 2”
“User Set 3”
198
Mode Direction Change
Unipolar Drive Logic
Bipolar Sign of Reference
Reverse Dis Not Changeable
xxx 1xxxxxxxxxxxx
10 01234567891112131415
1 =Save at Power Down
0 =Do Not Save
x =Reserved
Bit #
Factory Default Bit Values
At Powr Down
0xx 0xxxxxxxxxxxx
10 01234567891112131415
1 =Save at Power Down
0 =Do Not Save
x =Reserved
Bit #
Factory Default Bit Values
At Powr Down
At Stop