Instruction Manual

3-10 Programming and Parameters
Speed Command File
File
Group
No.
Parameter Name & Description
See page 3-2 for symbol descriptions
Values Related
SPEED COMMAND
Spd Mode & Limits
080 [Speed Mode]
Sets the method of speed regulation.
Default:
Options:
0
0
1
2
“Open Loop”
“Open Loop”
“Slip Comp”
“Process PI”
124 thru 138
081 [Minimum Speed]
Sets the low limit for speed reference after scaling is applied. Refer to
parameter 083 [Overspeed Limit].
Default:
Min/Max:
Units:
0.0
0.0/[Maximum Speed]
0.1 Hz
083, 092,
095
082 [Maximum Speed]
Sets the high limit for speed reference after scaling is applied. Refer to
parameter 083 [Overspeed Limit].
Default:
Min/Max:
Units:
50.0 or 60.0 Hz (volt class)
[Motor NP RPM]
5.0/400.0 Hz
0.1 Hz
055, 083,
091
, 094,
202
083 [Overspeed Limit]
Sets the incremental amount of the output frequency (above [Maximum
Speed]) allowable for functions such as slip compensation.
[Maximum Speed] + [Overspeed Limit] must be <
[Maximum Freq]
Default:
Min/Max:
Units:
10.0 Hz
0.0/20.0 Hz
0.1 Hz
055, 082
084
085
086
[Skip Frequency 1]
[Skip Frequency 2]
[Skip Frequency 3]
Sets a frequency at which the drive will not operate. [Skip Frequency 1-3]
and [Skip Frequency Band] must not equal 0.
Default:
Default:
Default:
Min/Max:
Units:
0.0 Hz
0.0 Hz
0.0 Hz
–/+[Maximum Speed]
0.1 Hz
087
087 [Skip Freq Band]
Determines the bandwidth around a skip frequency. [Skip Freq Band] is
split, applying 1/2 above and 1/2 below the actual skip frequency. The
same bandwidth applies to all skip frequencies.
Default:
Min/Max:
Units:
0.0 Hz
0.0/30.0 Hz
0.1 Hz
084, 085,
086
Allowable Output Frequency Range
Bus Regulation or Current Limit
Voltage
Frequency
Allowable Output Frequency Range
Normal Operation
Allowable Reference Frequency Range
Frequency Trim due to
Speed Control Mode
Max Volts
Motor Volts
Break Volts
Start Boost
Run
0 Min
Speed
Motor
Hz
Max
Speed
Output
Freq Limit
Max
Freq
Break
Frequency
Overspeed
Limit