Instruction Manual
2-4 Start Up
Running S.M.A.R.T. Start
During a Start Up, the majority of applications require changes to only a
few parameters. The LCD HIM on a LPM15 drive offers S.M.A.R.T. start,
which displays the most commonly changed parameters. With these
parameters, you can set the following functions:
S - Start Mode and Stop Mode
M - Minimum and Maximum Speed
A - Accel Time 1 and Decel Time 1
R - Reference Source
T - Thermal Motor Overload
To run a S.M.A.R.T. start routine:
Running an Assisted Start
Up
Important: This start-up routine requires an LCD HIM.
The Assisted start-up routine asks simple yes or no questions and prompts
you to input required information. Access Assisted Start Up by selecting
“Start Up” from the Main Menu.
To perform an Assisted Start-Up:
Step Key(s) Example LCD Displays
1. Press ALT and then Esc (S.M.A.R.T).
The S.M.A.R.T. start screen appears.
2. View and change parameter values as
desired. For HIM information, see
Appendix C.
3. Press Esc to exit the S.M.A.R.T. start.
ALT
Esc
Esc
F-> Stopped Auto
0.0
Hz
Main Menu:
Diagnostics
Parameter
SMART List:
Digital In2 Sel
Stop Mode A
Minimum Speed
Step Key(s) Example LCD Displays
1. In the Main Menu, press the Up Arrow
or Down Arrow to scroll to “Start Up”.
2. Press Enter.
F-> Stopped Auto
0.0
Hz
Main Menu:
Memory Storage
Start Up
Preferences