Owner's manual

Frame 3A and 3B Installation 3-25
PowerFlex 700L Frames 2, 3A, and 3B Liquid-Cooled AC Drives User Manual
Publication 20L-UM001E-EN-P
Table 3.B Frame 3 Power Terminal Specifications
Installing an External/Separate Input Disconnect
An input disconnect can be installed in the line before the drive input
terminals in accordance with local, national, and international codes (for
example, NEC/CEC). Size the disconnect according to the in-rush current
as well as any additional loads the disconnect might supply. Coordinate the
trip rating for the inrush current (10-12 times full load current) with that of
the input isolation transformer, if used. See Installing Transformers and
Reactors (Not Recommended) on page 3-23 for additional information.
Installing Power Wiring from Input Filter Bay to the Power Module Bay
Use the following steps to connect AC input power to the drive.
1. Connect the three-phase AC input power leads (three-wire 380-480V
AC or three-wire 600-690V AC, depending on drive nameplate voltage
rating) to the R/L1, S/L2, and T/L3 input power terminals on the drive:
Frame 3A Combined Converter/Inverter Power Module (for terminal
locations, see Figure 3.2
, Figure 3.18, and Figure 3.25).
Frame 3A Dual Inverter Power Module (for terminal locations, see
Figure 3.2
, Figure 3.18, and Figure 3.26).
Frame 3B Separate Converter Power Module (for terminal locations,
see Figure 3.3
, Figure 3.21, and Figure 3.27).
2. Tighten the AC input power terminal connections to the recommended
torque as shown in Table 3.C
.
Item Name Description
Frame
Size
Wire Size Range
(1)
Recommended Tightening
Torque (+
10%)
Maximum Minimum
Input Power Wire Lugs
R/L1, S/L2, T/L3
Input power
connections on drive
3A 400 MCM 3/0 42 Nm (375 lbin)
3B 1000 MCM 500 MCM 62 Nm (550 lbin)
PE Wire Lug Terminating point for
ground wires
3A or
3B
600 MCM #2 AWG 34 Nm (300 lbin)
(1)
Maximum/minimum sizes that the terminals will accept - these are not recommendations.
!
ATTENTION: Do not route signal and control wiring with
power wiring in the same conduit. This can cause interference
with drive operation. Failure to observe this precaution can result
in damage to, or destruction of, the equipment.